Model CT-3500

Operating Procedures

APPENDIX A

CT-3500

 Troubleshooting Guide

Item

Symptom

Possible Problem

Solution

1

CT-3500 will not
start timing.

1. No trigger voltage
detected.
2. Broken trigger lead.

1.Check trigger cable connection
to Trip and Close coil.
2. Inspect trigger cable cables.

2

CT-3500 displays
“Detect Standing
Voltage”.

1.There is standing voltage
across trigger input lead.
The CT-3500 expects a
voltage only when the
circuit breaker coil is
energized.

1. Check trigger-cable
connection to trip and close coil.
2. If there is standing voltage
across coil, check for lamp
(indicator) circuit.

3

Timing channels is
not working
correctly.

1. Bad contact cable
connection to breaker.
2. Missing common
connection on the breaker
bushing.

1 Check contact cable
connection to breaker.
2. Inspect contact leads.
3. Make sure the common side
(black lead) of contact bushing is
tied to ground.