3.3.4. Performing an On-Line Timing Test on Live Contacts

The optional "On-line" timing mode (part no. 9021-OT) can be used to capture the breaker's
trip or close time, the trip/close coil current “fingerprint”, and the battery supply voltage while
the breaker is still in service. The On-line timing mode requires an external trigger on the coil
being tested.

Follow the steps below to perform an on-line timing test (an OPEN test example is shown
below):

a. Make the cable connections per Figure 7 and then start from the "START-UP" menu:

Press the

[1]

key (TIME BREAKER).

b. The following screen will be displayed:

Press the

[2]

key (TIME LIVE CONTACTS).

c. The following screen will be displayed:

Press the

[1]

key (WINDOW = 1 SEC).

d. The following screen will be displayed:

TIMING MODE:

1. OPEN 2. CLOSE
3. O-C 4. C-O

TIMING WINDOW:

1. WINDOW = 1 sec
2. WINDOW = 10 SEC
3. WINDOW = 20 SEC

1. TIME DRY CONTACTS
2. TIME LIVE CONTACTS




1. TIME BREAKER 09/23/13
2. GET RESULTS 10:10:10
3. SAVE/RESTORE
4. SETUP
5. DIAGNOSTICS