REV 1 EZCT-2000B USER’S MANUAL
31
Press the
[1]
key (RUN TEST).
c. The following screen will be displayed:
Press the
[6]
key (BURDEN TEST ONLY).
d. The following screen will be displayed:
Use the alpha-numeric keypad to enter a test note and then press the
[ENTER]
key.
e. The following screen will be displayed:
Select the burden test current by pressing either the
[1]
key (1A) or the
[2]
key (5A).
f. The following screen will be displayed:
Press the
[START]
key to begin the test.
test 1 parameters:
1 amp burden test
connect x1-x2 cables
to burden now.
"Start" to begin
BURDEN TEST CURRENT
1.
1A
2.
5A
ENTER TEST 1 NOTE:
_
↑↓
to position
"ENTER" TO ACCEPT
1.
Res, excit & ratio
2.
excitation & ratio
3.
excitation only
4.
ratio only
5.
resistance & excit
6.
burden test only
7.
insulation tst only