Oitware-200 122, Oit to plc com mu ni ca tion 122, Oitware-200 – Maple Systems OIT Family User Manual

Page 122: Oit to plc communication

Advertising
background image

When the PLC Requests the Same Screen Twice the Screen is

Not Displayed

Possible Cause:

•

If the MRR already contained the screen number that the PLC requested, the OIT would

not recognize the screen request.

Possible Solution:

•

Modify the PLC program so that when the MRR already contains the screen number that

the PLC is requesting, the PLC writes a zero to the MRR before writing the screen number.

•

If using an OIT3100 and OIT4100 Series, activate the Clear Register/Bit After Receiving

Screen Request feature. Refer to the Configuring the MRR with Enhanced Features

section in CHAPTER 5: Displaying Stored Screens.

OITware-200

PC Displays “Out of Memory” When Starting OITware-200

Possible Cause:

•

The computer does not have sufficient resources to run OITware-200.

Possible Solution:

•

Use a computer that has at least 4MB of RAM.

OITware-200 Displays “Timeout Detected. OIT did not respond.”

Possible Causes:

•

The OIT is not connected to the PC or is not in Download/Upload Mode.

•

OITware-200 is not using the correct COM port.

•

The configuration cable is not wired correctly.

•

The configuration cable is not connected to the correct port on the OIT or the PC.

•

If your OIT has two serial ports, something is connected to the RTS/CTS lines on port 1.

Possible Solutions:

•

Verify that the configuration cable is wired correctly and is in good condition.

•

Follow the steps in the Downloading an OITware-200 Project section in CHAPTER 1:

Getting Started.

•

Ifyour OIThas two serialports,verifynothingis connectedto the RTS/CTSlines onport1.

OIT to PLC Communication

OIT Displays “Cannot Connect To PLC During Startup.

*** Reconnect in progress ***” or

“Can’t connect to PLC. Retry in Progress!”

Possible Causes:

•

The PLC’s mode switch is not in the correct position.

•

The PLC password in the OIT does not match the PLC.

•

The communication settings (baud rate, parity, data bits, stop bits) for the OIT and PLC do

not match.

•

The communication cable is not wired correctly.

•

The communication cable is not connected to the correct port on the OIT or PLC.

•

The wrong PLC protocol was downloaded to the OIT

Troubleshooting

122

1010-0099, Rev. 07