Possible Solutions:

•

Verify that your PLC’s mode switch (if applicable) is in the correct position. The switch may need

to be in a mode other than run mode; such as terminal mode or xxxxxx mode. Refer to your

controlleroperationsmanualortheapplicableControllerInformationSheetfromMapleSystems.

•

Verify that the PLC password in the OIT matches the password in your PLC. In

OITware-200 press F4 to open the OIT - Controller Settings dialog box. In the Password

group box, enter the correct PLC password.

•

Verify that the communication settings in the OIT and PLC match. In OITware-200 press

F4 to open the OIT - Controller Settings dialog box. In the OIT - Controller Serial

Communications Settings group box, select the correct communication settings.

•

Verify that the communication cable is wired correctly and in good condition.

•

Verify that the OIT and PLC are connected correctly. Refer to the Installation Manual that

came with the OIT.

•

Download the project with the correct PLC protocol from OITware-200. Follow the steps

in the Downloading an OITware-200 Project section in CHAPTER 1: Getting Started.

OIT Displays “Cannot write to Msg Request Register!” or “Er-

ror: Setting up Mailbox During Startup”

Possible Cause:

•

The PLC address for the Message Request Register (MRR) is outside the memory

supported by the PLC’s CPU.

Possible Solution:

•

Change the PLC address for the MRR. In OITware-200 press SHIFT+F6 to open the OIT

Message Control Settings dialog box. In the Message Request Register group box, select a

supported PLC address. If you are using the MRR enhanced features, to set the PLC

address(es) for the MRR(s), refer to the Configuring the MRR section in CHAPTER 5:

Displaying Stored Screens.

OIT Displays “Cannot write to the Status Coils!” or

“Error: Setting up StatusCoils On Startup” or

“Cannot set the Reset Status Coil!” or

“Error: Setting STAT_RESET during Startup” or

“Cannot set the Alarm Empty Status Coil!” or

“Error: Setting ALM_EMPTY During Startup”

Possible Cause:

•

The PLC address for the Status Coils is outside the memory supported by the PLC’s CPU.

Possible Solution:

•

Change the PLC address for the Status Coils. In OITware-200 press F4 to open the OIT -

Controller Settings dialog box. In the Status Coils group box, select a supported PLC

address.

OIT Displays “Cannot write to the Function Key Coils!” or

“Error: Setting up KeyCoils On Startup”

Possible Cause:

•

The PLC address for the Function Key Coils is outside the memory supported by the

PLC’s CPU.

Possible Solution:

•

Change the PLC address for the Function Key Coils. In OITware-200 press F5 to open the

Function Key Editor dialog box. In the Coil Address group box, select a supported PLC

address.

Troubleshooting