Watlow EZ-ZONE RMC User Manual

Page 102

Advertising
background image

Watlow EZ-ZONE

®

RMC Module

99

Chapter 4 Setup Page

RMC Module • Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

& Read/

Write

[SFn;b]
[SFn.b]

Logic (1 to 4)

Source Function B

Set the type of function

that will be used for this

source.

[none]

None (61)

[ALM]

Alarm (6)

[`C;Pr]

Cool Power, Control

Loop (161)

[`CPE]

Compare (230)

[`Ctr]

Counter (231)

[`dio]

Digital I/O (1142)

[Ent;A]

Profile Event Out A

(233)

[Ent;b]

Profile Event Out B

(234)

[Ent;C]

Profile Event Out C

(235)

[Ent;d]

Profile Event Out D

(236)

[Ent;E]

Profile Event Out E

(247)

[Ent;F]

Profile Event Out F

(248)

[Ent;g]

Profile Event Out G

(249)

[Ent;h]

Profile Event Out H

(250)

[`FUn]

Function Key (1001)

[lim]

Limit (126)

[`lgC]

Logic (239)

[SoF;1]

Special Function Output

1 (1532)

[SoF;2]

Special Function Output

2 (1533)

[SoF;3]

Special Function Output

3 (1534)

[SoF;4]

Special Function Output

4 (1535)

[tMr]

Timer (244)

[`uAr]

Variable (245)

None

3682

[offset 80]

0x7F (127)

1 to 4

2

- - - -

27002

uint
RWES

[`Si;B]
[ Si.b]

Logic (1 to 4)

Source Instance B

Set the instance of the

function selected above.

1 to 250

1

3698

[offset 80]

0x7F (127)

1 to 4

0xA (10)

- - - -

27010

uint
RWES

{`S2;B]
[ SZ.b]

Logic (1 to 4)

Source Zone B

Set the zone of the func-

tion selected above

0 to 16

0

3714

[offset 80]

0x7F (127)

1 to 4

0x12 (18)

- - - -

27018

uint
RWES

Note:

Some values will be rounded off to fit in the four-character display .

Full values can be read with other interfaces .

Note:

If there is only one instance of a menu, no submenus will appear .

** These parameters/prompts are available in these menus with firmware revisions 6 .0 and

above .

R: Read

W: Write

E:

EEPROM

S:

User Set