Watlow EZ-ZONE RMC User Manual
Page 59

Watlow EZ-ZONE
®
RMC Module
•
56
•
Chapter 3 Operations Page
RMC Module • Operations Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[t;SP3]
[t.SP3]
Profile Status
*Target Set Point
Loop 3
View or change the
target set point of the
current step.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
0.0°F
or
units
-18.0°C
5376
0x7A
(122)
1
0x31 (49)
- - - -
22049
float
RW
[t;SP4]
[t.SP4]
Profile Status
*Target Set Point
Loop 4
View or change the
target set point of the
current step.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
0.0°F
or
units
-18.0°C
5378
0x7A
(122)
1
0x32 (50)
- - - -
22050
float
RW
[P;SP1]
[P.SP1]
Profile Status
Produced Set Point 1
Display the current set
point, even if the profile
is ramping.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - -
5288
- - - -
- - - -
22005
float
R
[P;SP2]
[P.SP2]
Profile Status
Produced Set Point 2
Display the current set
point, even if the profile
is ramping.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - -
5380
- - - -
- - - -
22051
float
R
[P;SP3]
[P.SP3]
Profile Status
Produced Set Point 3
Display the current set
point, even if the profile
is ramping.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - -
5382
- - - -
- - - -
22052
float
R
[P;SP4]
[P.SP4]
Profile Status
Produced Set Point 4
Display the current set
point, even if the profile
is ramping.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - -
5384
- - - -
- - - -
22053
float
R
No Dis-
play
Profile Status
Produced Control
Mode 1
Display the current
control mode.
Off (62)
Auto (10)
Manual (54)
- - - -
5366
0x7A
(122)
1
0x2C (44)
- - - -
22044
uint
R
No Dis-
play
Profile Status
Produced Control
Mode 2
Display the current
control mode.
Off (62)
Auto (10)
Manual (54)
- - - -
5368
0x7A
(122)
1
0x2D (45)
- - - -
22045
uint
R
No Dis-
play
Profile Status
Produced Control
Mode 3
Display the current
control mode.
Off (62)
Auto (10)
Manual (54)
- - - -
5370
0x7A
(122)
1
0x2E (46)
- - - -
22046
uint
R
No Dis-
play
Profile Status
Produced Control
Mode 4
Display the current
control mode.
Off (62)
Auto (10)
Manual (54)
- - - -
5372
0x7A
(122)
1
0x2F (47)
- - - -
22047
uint
R
Note:
Some values will be rounded off to fit in the four-character display . Full values can be
read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0
and above .
R: Read
W: Write
E: EEPROM
S: User Set