Resetting a tripped limit, Alarm latching, Alarm silencing – Watlow EZ-ZONE RMC User Manual

Page 167: Alarm blocking

Advertising
background image

Watlow EZ-ZONE

®

RMC Module

164

Chapter 7 Features

Alarm Latching

A latched alarm will remain active after the alarm

condition has passed. It can only be deactivated by

the user and only when the alarm condition no longer

exists.

If using an RUI an active message, such as an

alarm message, will cause the display to toggle be-

tween the normal settings and the active message in

the upper display and [Attn] in the lower display. To

clear a latched alarm:
1. Push the Advance Key

to display [ignr] in the

upper display and the message source in the lower

display.

2. Use the Up ¿ or Down ¯ keys to scroll through

possible responses, such as Clear [`CLr] or Silence
[`SiL]

.

3. Push the Advance

or Infinity ˆ key to execute

the action.

Without an RUI, a latched alarm can be reset by

cycling power to the module or configuring an Ac-

tion function within the control to perform a reset.

Do this by setting the Action Function to alarm and

trigger the Action to occur through Source Function

A.
An alarm that is not latched (self-clearing) will de-

activate automatically when the alarm condition has

passed. Turn Alarm Latching [`A;LA] on or off via

the Setup Page, Alarm Menu.

Normal Operating Range

Alarm High

Set Point

Time

Temperature

Alarm Low

Set Point

Alarm Response with Hysteresis

The alarm state continues until the

temperature drops to the Alarm High

Set Point minus the hysteresis. A

latching alarm could be turned off by

the operator at this point. A

non-latching alarm would turn off

automatically.

The alarm state begins when the temperature

reaches the Alarm High Set Point

Process

Temperature

Alarm Hysteresis

Alarm Silencing

If alarm silencing is on the operator can disable the

alarm output while the controller is in an alarm

state. The process value or temperature has to enter

the normal operating range beyond the hysteresis

zone to activate the alarm output function again.

If using an RUI an active message, such as an

alarm message, will cause the display to toggle be-

tween the normal settings and the active message in

the upper display and [Attn] in the lower display. To

silence an alarm:
1. Push the Advance Key

to display [ignr] in the

upper display and the message source in the lower

display.

2. Use the Up ¿ and Down ¯ keys to scroll through

possible responses, such as Clear [`CLr] or Silence
[`SiL]

.

3. Push the Advance

or Infinity ˆ key to execute

the action.

Without an RUI, silencing aa alarm can be accom-

plished by configuring an Action function within the

control to silence the alarm. Do this by setting the

Action Function to Silence and trigger the Action to

occur through Source Function A.

Turn Alarm Silencing [`A;Si] on or off via the

Setup Page, Alarm Menu.

Alarm Blocking

Alarm blocking allows a system to warm up after

it has been started up. With alarm blocking on, an

alarm is not triggered when the process tempera-

ture is initially lower than the alarm low set point

or higher than the alarm high set point. The process

temperature has to enter the normal operating range

beyond the hysteresis zone to activate the alarm

function.

If the RMC module has an output that is function-

ing as a deviation alarm, the alarm is blocked when

the set point is changed, until the process value re-

enters the normal operating range.

Turn Alarm Blocking [`A;bL] on or off via the

Setup Page, Alarm Menu.

Resetting a Tripped Limit

When a limit controller is ordered (RMC[5,6] _ [5,6] _

[5,6] _ [5,6] _ _ _ _ _) output 2 (digit 4), output 4 (digit

6), output 6 (digit 8) or output 8 (digit 10) will always

be a Form A (normally open) Mechanical Relay and

it will always be internally tied to the limit function.

When the limit is in a safe state the internal coil for

this relay will be energized, therefore the relay will

be closed. When a condition occurs that causes the

limit to trip, the internal coil will deengerize caus-

ing the relay to latch open. When the condition that

caused the limit to trip has been resolved, the relay

will remain latched open until reset. The process to

reset a latched limit can be different from control to

control and is dependent upon the controller firm-

ware version.
To check the firmware revision of your control do

one of the following:
If Used in Conjunction with an Remote User In-

terface
1. Navigate to the RMC Factory Page by simultane-

ously pushing and holding the Advance Key

and the Infinity ˆ for approximately 8 seconds

and then use the up or down arrow key to navigate

to the Diagnostic Menu. Once there, push the Ad-

vance Key twice where the revision [`reu] will be

shown in the lower display and the upper display

will indicate the current firmware revision.

Advertising