Control function, Watlow ez-zone, Rmc module – Watlow EZ-ZONE RMC User Manual

Page 179: Chapter 7 features

Advertising
background image

Watlow EZ-ZONE

®

RMC Module

176

Chapter 7 Features

Control Function

Control

Overview

Instances - 1 to 4 per RMC

Control Mode

Remote Set P

oint Enable

Remote Set P

oint Enable

Remote Set P

oint

Type

User F

ailure

Action

Loop Error Clear Request

Input Error F

ailure

Fixed P

ower

Open Loop Detect Enable

Open Loop Detect

Time

Open Loop Detect Deviation

Ramp

Action

Ramp Scale

Ramp Rate

Profiling Enable

Closed Loop Low Set P

oint

Set P

oint

Open

Limit

Low

Closed Loop High Set P

oint

Set P

oint

Open

Limit

High

Heat

Algorithm

Cool

Algorithm

TRU-TUNE+ Enable

Autotune

Aggressiveness

Peltier Dela

y

TRU-TUNE+ Band

TRU-TUNE+ Gain

Cool Output Curve

Autotune Set P

oint

Autotune

Closed Loop Set P

oint

Idle Set P

oint

Heat Proportional Band

Cool Proportional Band

Heat Hysteresis

Cool Hysteresis

Deadband

Open Loop Set P

oint

Cool Power

Heat Power

Tune Status

Loop Error

Closed Loop Set Point

Open Loop Set Point

Loop Power

Process Value Active

Source Function A
Source Instance A
Source Zone A
Source Error A

Source Function B
Source Instance B
Source Zone B
Source Error B

Time Integral

Time Derivative

[SFn;A]

Source Function A : Analog Input, Process Value

`[h;Ag]

Heat Algorithm : Off, PID, On/Off

[`C;Ag]

Cool Algorithm : Off, PID, On/Off

[t;tUn]

TRU-TUNE+ Enable : No, Yes

[t;bnd]

TRU-TUNE+ Band : 0 to 100

[`t;gn]

TRU-TUNE+ Gain : 1 to 6

[t;Agr]

Autotune Aggressiveness : Under, Critical, Over

[`r;En]

Remote Set Point Enable : No, Yes

[`Si;b]

Source Instance B (Remote Set Point Source Instance) : 1 to 250

[`S2;b]

Source Zone B : 0 to 16

[MAn]

Fixed Power : -100.0 to 100.0 %

[`L;dE]

Open Loop Detect Enable : No, Yes

[`L;dt]

Open Loop Detect Time : 0 to 3,600 seconds

[``rP]

Ramp Action : Off, Startup, Set Point, Both

[`r;SC]

Ramp Scale : Hours, Minutes

[`r;En]

Remote Set Point Enable : No, Yes

[`C;M]

Control Mode : Off, Auto, Manual

[A;tSP]

Autotune Set Point : 50 to 200 %

[`AUt]

Autotune : No, Yes

[`C;SP]

Closed Loop Set Point : -1,999.000 to 9,999.000

[`id;S]

Idle Set Point : -1,999.000 to 9,999.000

[`h;Pb]

Heat Proportional Band : 0.001 to 9,999.000

[`h;hy]

Heat Hysteresis : 0.001 to 9,999.000

[`C;Pb]

Cool Proportional Band : 0.001 to 9,999.000

[`C;hy]

Cool Hysteresis : 0.001 to 9,999.000

[``ti]

Time Integral : 0 to 9,999 seconds

[``td]

Time Derivative : 0 to 9,999 seconds

`[C;Cr]

Cool Output Curve : Off, Non-linear curve 1, Non-linear curve 2

[`r;ty]

Remote Set Point Type : Auto, Manual

[`L;SP]

Low Set Point : -1,999.000 to 9,999.000

[`h;SP]

High Set Point : -1,999.000 to 9,999.000

[SP;Lo]

Set Point Open Limit Low : -100.0 to 100.0 %

[SP;hi]

Set Point Open Limit High : -100.0 to 100.0 %

[`L;dd]

Open Loop Detect Deviation : -1,999.000 to 9,999.000

[`r;rt]

Ramp Rate : 0.000 to 9,999.000

[Pro;E]

Profiling Enable: No, Yes

[``db]

Deadband : -1,000.000 to 1,000.000

[`o;SP]

Open Loop Set Point : -100.0 to 100.0 %

[`iS;A]

Source Instance A : (not changeable)*

[LooP]

Loop Menu

[`SEt]

Setup Page

[LooP]

Loop Menu

[oPEr]

Operation Page

[`P;dL]

Peltier Delay : 0.0 to 5.0

Note: Control Loop primary source instance must match

Process Value or Analog Input instance.

Loop Power : -100.0 to 100.0 %
Loop Error: None, Open Loop, Reversed Sensor
Loop Error Clear Request : Ignore, Clear
Tune Status : Off, Cross 1 Positive, Cross 1 Negative,

Cross 2 Positive, Cross 2 Negative, Cross 3 Positive,

Cross 3 Negative, Measuring Max, Measuring Min,

Calculating, Complete, Timeout

[C;MA]

Control Mode Active : Off, Auto, Manual

[`h;Pr]

Heat Power : 0.0 to 100.0 %

[`C;Pr]

Cool Power : 0.0 to 100.0 %

[`C;SP]

Closed Loop Set Point : -1,999.000 to 9,999.000

[`Pu;A]

Process Value Active : -1,999.000 to 9,999.000

[Mon]

Monitor Menu

[oPEr]

Operation Page

Control Mode Active

[SFn;b]

Source Function B : (Remote Set Point Source) : None, Analog

Input, Current, Cool Power, Heat Power, Power, Linearization,

Math, Process Value, Set Point Closed, Set Point Open, Variable

[fail]

Input Error Failure : Off, Bumpless Transfer, Manual Power,

User

[`Ufa]

User Failure Action : Off, Bumpless Transfer, Manual Power,

User

Advertising