Modbus registers, Modbus registers -1 – Yokogawa RotaMASS 3-Series User Manual

Page 53

Advertising
background image

IM 01R04B08-00E-E 1st edition February 15, 2012 -00

All Rights Reserved. Copyright © 2012, Rota Yokogawa

<7. MODBUS REGISTERS>

7-1

7. MODBUS REGISTERS

All available parameters are assigned to holding registers wherein the measurement values and units
are assigned to input registers on Modbus. A list of all available parameters and registers for Modbus
communication option /MB1 can be found in the table below. The table contains also the selection values
which can be written to selection parameters. Holding registers start at 40000h, input registers at 30000h.

Parameter

Data range

Selection
value

Unit

Read

Holding

Register

Input

Register

Write
Execute

Address (decimal)

Mass Flow

-

-

Mass flow unit

R

528

0

Volume Flow

-

-

Vol flow unit

R

544

2

Density

-

-

Density unit

R

560

4

Temperature

-

-

Temperature unit

R

576

6

F-Total flex

-

-

Total flex unit

R

592

8

R-Total flex

-

-

Total flex unit

R

608

10

D-Total flex

-

-

Total flex unit

R

624

12

F-Total mass

-

-

Total mass unit

R

640

14

R-Total mass

-

-

Total mass unit

R

656

16

D-Total mass

-

-

Total mass unit

R

672

18

F-Total vol

-

-

Total volume unit

R

688

20

R-Total vol

-

-

Total volume unit

R

704

22

D-Total vol

-

-

Total volume unit

R

720

24

F-Total net

-

-

Total net unit

R

736

26

R-Total net

-

-

Total net unit

R

752

28

D-Total net

-

-

Total net unit

R

768

30

Concentration meas

0 to 110

-

Concentration meas unit

R

784

32

Net flow

-

-

Mass flow unit

R

800

34

F-Total energy

-

-

Total unit energy

R

816

36

Velocity

-

-

Velocity unit

R

832

38

Total reset cntrl

Inhibit

0

-

R/W

848

Enable

1

Total reset

Not Execute

0

-

R/W

864

Reset flex totals

1

Reset mass totals

2

Reset volume totals

3

Reset net totals

4

Reset all totals

5

Error group1/2

0 to 255

 -

-

R

896

42

Alarm group1/2

0 to 255

 -

-

R

912

43

Warning group1/2

0 to 255

 -

-

R

928

44

Autozero tuning

Inhibit

0

-

R/W

960

Enable

1

Autozero Time

3 min

0

-

R/W

976

30 s

1

Autozero Exe

Not Execute

0

-

Exe

992

Execute

1

Autozero Value

depends on size

 

kg/h

R

1008

Flow direction

Forward

0

-

R/W

1056

Reverse

1