<8. TECHNICAL DETAILS OF MODBUS COMMUNICATION>

8-1

8. TECHNICAL DETAILS OF MODBUS

COMMUNICATION

8.1 Range check

According to the Modbus specification error bit and exception codes are only defined for physical
transmission errors. Therefore there is no possibility to signal logical errors like violation of data ranges or
invalid selections at the time when a register is being written.
ROTAMASS 3 Series Modbus communication type will check all values written via Modbus. Values which
are invalid or out of range will not be stored and the previous content of the register will be kept and
returned to the host. Therefore the master will have to check the data in the response of the write command.
However, this will not work for values which consist of two or more registers like float values. When writing
multiple registers the data will not be returned and as a consequence the master will not be able to check
it. Therefore to make sure if these values are accepted and stored in the device the only solution is to read
back the value after writing using another read command!
For details of Modbus communication refer to the specification

http://www.modbus.org/docs/Modbus_Application_Protocol_V1_1b.pdf

8.2 Byte order of transmission

This section describes the transmission of float values which consist of two registers. In case of differences
in the memory model of ROTAMASS 3 Series Modbus communication type and the host system it might be
necessary to swap registers and/or single bytes.
The following illustration shows the storage of a float value in the IEE-754 format and the order of
transmission in Modbus protocol on a typical example.
The mass flow value in user unit (holding register 528/529 decimal or 210/211 hex) should be read using
Modbus command 3:

Storage in registers:

Float value

44.996628

Byte number

Byte 3 Byte 2 Byte 1 Byte 0

Values in hex in
IEEE-754 notation

42

33

FC

8C

Register no.

529 dec.

(211 hex)

528 dec.

(210 hex)

Transmission via Modbus (all values in hex):

Request
from
host

Device

address

Modbus

command

Start

address

Number of

registers

Checksum

01

03

02 10

00 02

C4 76

Response
from
ROTAMASS

Device

address

Modbus

command

Number

of bytes

Data

Checksum

01

03

04

44.996628

7B 3D

Byte 1

Byte 0

Byte 3

Byte 2

FC

8C

42

33

Reg. 528 dec.

(Reg. 210 hex)

Reg. 529 dec.

(Reg. 211 hex)

Because of the order of transmission the registers eventually need to be swapped to get the float value in
the standard IEEE-754 format. Commercially available software might do this automatically. However, those
users who intend to write their own communication software must be aware of the order of transmission when
reading multiple registers and swap registers and/or bytes if necessary!