<6. Operation>

6-5

IM 01C27H01-01EN

(a) Deep sleep

F0607.ai

(b) Ready and pause

F0608.ai

(c) Confirm connecting status

F0609.ai

(d) Join

F0610.ai

NOTE

If the transmitter searches the Field Wireless

Network for long time at low ambient

temperature condition, sometimes error “AL.70

LOWBAT” is displayed on the Integral Indicator.

Even though using new batteries, it can occur. It

occurs because of battery characteristics.

After joining to the Field Wireless Network, this

error will be cleared within one hour if battery has

no failure.

6.5 Shutting Down The

Transmitter

When shut down the transmitter, remove the battery

pack or set the transmitter to deep sleep mode by

the Device Configuration Tool.

NOTE

Whenever shutting down the transmitter for a

long period, detach the transmitter (diaphragm

seals) from the tank

• Refer to subsection 8.4.4 “Replacing the

Battery Pack” for the battery pack removing.

• When storing the instrument with a battery

pack inserted, it is recommended to put the

instrument into deep sleep mode to conserve

battery power. For details on how to switch to

deep sleep mode, refer to subsection 7.3.16

“Switching to the Deep Sleep Mode”.

6.6 Venting or Draining

Transmitter Process-

Detector Section

If condensate (or gas) collects in the transmitter

process-detector section, the measured pressure

may be in error. If it is not possible to configure the

piping for self draining (or self-venting) operation,

you will need to loosen the drain (vent) screw on the

flushing connection ring to completely drain (vent)

any stagnated liquid (gas).

However, since draining condensate or bleeding off

gas gives the pressure measurement disturbance,

this should not be done when the loop is in

operation.