<8. Maintenance>

8-8

IM 01C27H01-01EN

8.5.2 Troubleshooting Flowcharts

Check display of the error code.

Check self-diagnostics by the device configuration tool.

Does the self-diagnostic

indicate problem location?

Contact Yokogawa service personnel.

F0806.ai

The following sorts of symptoms indicate that transmitter

may not be operating properly.

Example : • There is no output signal.

• Output signal does not change even though

process variable is known to be varying.

• Output value is inconsistent with value

inferred for process variable.

Fix pressure leaks, paying particular

attention to connections for

pressure-detector section.

Is there any pressure leak?

YES

NO

YES

NO

Refer to Alarm Message Summary in

Subsection 8.5.3.

Is the Field Wireless Network

setting correct?

NO

YES

Reconnect to the Field Wireless

Network.

Connect the device configuration tool and check self-diagnostics.

Does the self-

diagnostic indicate problem

location?

Contact Yokogawa service personnel.

F0807.ai

Are high

and low pressure side

diaphragm seals correctly

connected to the

process?

Refer to Alarm Message Summary

in Subsection 8.5.3

YES

NO

Use the transmitter within the

measurement range shown on the

data plate.

Correct the connections.

NO

YES

YES

Adjust the zero point.

NO

NO

YES

Is the liquid level as specified?

Is zero point

adjusted correctly?

Output travels beyond 0% or 100%.