<10. General Specifications>

10-1

IM 01C27H01-01E

10. General Specifications

10.1 Standard Specifications

Communication protocol

ISA100.11a protocol

Data rate

250 kbps

Frequency

2400 - 2483.5 MHz license free ISM band

Radio security

AES 128 bit codified

RF Transmitter power

Max. 11.6 dBm (fixed)

Antenna

+2 dBi Omni directional monopole type

Span and range limits
EJX118B

Measurement

Span/Range

M

H

2 to 100

–500 to 500

Span

Span

Range

Range

kPa

8 to 400

–400 to 400

–2000 to 2000

40 to 2000

–100 to 100

10 to 500

20 to 1000

–5000 to 5000

–1000 to 1000

100 to 5000

inH

2

O(/D1)

mbar(/D3)

mmH

2

O(/D4)

200 to 10000

–10000 to 10000

0.1 to 5 kgf/cm

2

–5 to 5 kgf/cm

2

T01E.ai

EJX438B

Span

Flush

type

*1

Extended

type

*1

–1 to 160

1.6 to 160

–1 to 35

23 to 1000 1.6 to 70

0.16 to 7

Span

Range

Range

0.16 to 16
–0.1 to 16

–0.1 to 3.5 –14.5 to 500

–14.5 to 2300

0.035 to 3.5

5 to 500

Span

23 to 2300

MPa

–0.1 to 7

–14.5 to 1000

Range

–1 to 70

1.6 to 160

–1 to 35

1.6 to 70

–1 to 70

–1 to 160

kgf/cm

2

(/D3)

psi (/D1)

bar (/D2)

0.35 to 35

0.35 to 35

Measurement

Span and Range

A

*1

T02E.ai

B

2

*1:

Measurement range is within the flange rating.

Performance specifications

Refer to GS01C27H01-01EN

Update Time

Measurement

mode

Differential

pressure

Pressure

Continuous

100 ms

100 ms

Intermittent

0.5 to 3600 s

selectable

0.5 to 3600 s

selectable

For amplifier housing code 7:

The transmitter shifts to the countinuous mode

when the update time is set to 1 second.

Minimum update time is 1 second.

For amplifier housing code 8 and 9:

The transmitter shifts to the countinuous mode

when the update time is set to 0.5 second.

Power Supply Specifications

Battery:

Use the dedicated battery pack.

Rated voltage: 7.2 V

Rated capacity: 19 Ah

Output

Wireless (ISA100.11a protocol) 2.4 GHz signal.

Output mode for EJX118B, linear or square

root, is selectable.

Zero Adjustment Limits

Zero can be fully elevated or suppressed, within

the lower and upper range limits of the capsule.

External Zero Adjustment

External Zero is continuously adjustable with

0.01% incremental resolution of span. Re-range

can be done locally using the digital indicator

with range-setting switch.

Integral Indicator (LCD display)

5-digit numerical display, 6-digit unit display and

bar graph.

The indicator is configurable to display one

or up to three of the following variables

periodically.; Differential pressure, static

pressure, temperature.

Self Diagnostics

Capsule failure, amplifier failure, configuration

error, battery alarm, wireless communication

alarm and over-range error for process

variables.

Capillary Fill Fluid Density Compensation

Compensation of the zero shift by the ambient

temperature effect on the capillary tube.

Ambient Temperature Limits

-40 to 85°C (-40 to 185°F)

-30 to 80°C (-22 to 176°F) LCD visible range

Note: The ambient temperature limits must be within the fill fluid

operating temperature range, see table 10.1.

Process Temperature Limits

See table 10.1.