2 test procedures, Test procedures -3, Insulation resistance test – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 12: Withstand voltage test

Advertising
background image

2-3

SM 04L31A01-01E

Testing

2

2.2

Test Procedures

Insulation Resistance Test

Perform this test using a DC 500 V insulation resistance meter and confirm that the

results meet the criteria below.

Terminals

Reference Values

Notes

Power terminal to earth terminal

100 M

or higher

Short all channels prior to test

Measurement input terminal to
earth terminal
Control input terminal to earth
terminal

RS-422-A/485 SG terminal to

100 M

or higher

Test only if the basic

RS-422-A/485 FG terminal

specification code for the
communications port is -2.

Ethernet input/output terminal

100 M

or higher

Short all terminals prior to test

to earth terminal

Withstand Voltage Test

Perform the test using a withstanding voltage tester and confirm that the results meet the

criteria below, and that the instrument does not malfunction.

Terminal

Reference Values

AC power terminal to earth terminal*

Leakage current of 10 mA or less at 1.5 kV AC for 1 minute

DC power terminal to earth terminal (/P1)*

Leakage current of 10 mA or less at 0.5 kV AC for 1 minute

Measurement input terminal to earth terminal

Leakage current of 2 mA or less at 1.5 kV AC for 1 minute

Control input terminal to earth terminal

Leakage current of 2 mA or less at 1.5 kV AC for 1 minute

Between measuring input terminals

Leakage current of 1 mA or less at 1 kV AC for 1 minute

Between control input terminals

Leakage current of 1 mA or less at 1 kV AC for 1 minute

Current and voltage pulse to earth terminal

§

Leakage current of 2 mA or less at 1 kV AC for 1 minute

Control relay terminal to earth terminal

Leakage current of 2 mA or less at 1.5 kV AC for 1 minute

(2, 4, and 6 loop models)

||

DO relay terminal to earth terminal

Leakage current of 2 mA or less at 1.5 kV AC for 1 minute

(2, 4, and 6 loop models)

#

DO(Tr) terminal to earth terminal

Leakage current of 2 mA or less at 0.5 kV AC for 1 minute

(2, 4, and 6 loop models or /CST1)**

D1 terminal to earth terminal

Leakage current of 2 mA or less at 0.5 kV AC for 1 minute

(2, 4, and 6 loop models or /CST1)

††

Alarm relay terminal to earth terminal

Leakage current of 2 mA or less at 1.5 kV AC for 1 minute

(/A6, /A6R, /A4F, /A4FR)

‡‡

Remote terminal to earth terminal (/A6R, /A4FR)

§§

Leakage current of 2 mA or less at 0.5 kV AC for 1 minute

24 V transmitter power supply output to earth terminal Leakage current of 10 mA or less at 0.5 kV AC for 1 minute
(/TPS4)

||||

*

Short L and N (or +/– with the /P1 option)

Short all channels

Short the + and – input terminals (except for the RTD b terminal)

Short the even and odd channels (for example, short channels 1-3-5 and 2-4-6 on the CX1000 or channels 1-3-

5-7-9 and channels 2-4-6-8-10 for the CX2000), and test the withstanding voltage between them.

§

Short mA, PULS, and C.

||

Short NO, NC, and C on CTRL OUT.

#

Short 1NO, 1C, and 2NO on DO.

**

Short DO3—DO6 and C.

†† Short all DI terminals.

‡‡ Short all alarm relay terminals.

§§ Short all remote terminals.

|||| Short all transmitter power supply output terminals (+/–).