3 troubleshooting checklist, Troubleshooting checklist -3 – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 34

Advertising
background image

SM 04L05A01-01E

5-3

Troubleshooting

5

5.3

Troubleshooting Checklist

Trouble

Operational

Check

Adjust

Exchange

Check Item

Power cable connection
Fuse is blown (/P1 option only)
Power ass’y
CPU ass’y
Memory ass’y
Display ass’y

CPU ass’y
Memory ass’y
Display ass’y
Optional terminal ass’y

Battery connector is disconnected?
Battery voltage is low (less than +3.0V)
CPU ass’y
Memory ass’y
Display ass’y

FFC ass’y of the keyboard is
disconnected/broken
Keyboard ass’y
CPU ass’y
Memory ass’y
Display ass’y

FFC ass’y of the LCD is disconnected/
broken
CPU ass’y
Memory ass’y
Display ass’y
LCD ass’y
Input wiring is disconnected
Noise
A/D ass’y
Scanner ass’y

Input is disconnected
Noise
Terminal cover is removed
RJC INT/EXT setting
A/D board ass’y
Input terminal
Scanner board ass’y

Power frequency setting is incorrect
Noise

Floppy disk/Zip disk/PC card drive unit

Power is not
turned ON

FAIL state

Memory cannot
be backed up

Panel key operation
is not normal

LCD is not normal

Measured value

incorrect

Measured

temperature

is incorrect

Measured value
fluctuates

External storage
media is not normal

Advertising