CTRL Module Assembly Tests

This section describes the test procedure for CTRL MODULE ASSY (B8700CL,

B8700CM, B8700CN, and B8700FT) which is used on the CX2000. This test is not

necessary if you will perform the general tests in section 2.2. Perform this test on the

module by itself.

Test Instruments

Instrument

Specifications

DC current meter

Accuracy: 0.01% of rdg

Withstanding voltage tester

AC 1 to 3 kV, 500 VDC

Oscilloscope

200 kS/s or more, isolated input

Resistor

250

Ω ±

1%

Jig

A measurement instrument having the same functions and
characteristics as the CX2000 or CX1000.

Tests

• Withstand Voltage Test

Consult your nearest Yokogawa representative regarding the following tests.

• Output Accuracy Test

• Voltage Pulse Output Test

• Control Relay Output Test

• DI Test

• DO Test

Testing Environment

Ambient temperature of 23

±

5

°

C, relative humidity of 55

±

20%

CAUTION

• Before starting the test, allow the instrument to warm up for 30 minutes or more.

• Make sure the module is installed in the CX1000/CX2000.

Test Procedure

Perform a withstand voltage test on the module installed in the CX1000/CX2000 at the

points listed below.

Test Points

Reference Values

Current and voltage pulse output to earth terminal on

Leakage current of 2 mA or less at 1 kV AC for 1 minute

the CX1000/CX2000*

Control relay terminal to CX1000/CX2000 earth terminal

Leakage current of 2 mA or less at 1.5 kV AC for 1 minute

DO relay terminal to CX1000/CX2000 earth terminal

Leakage current of 2 mA or less at 1.5 kV AC for 1 minute

DO (Tr) relay terminal to CX1000/CX2000 earth terminal

§

Leakage current of 2 mA or less at 0.5 kV AC for 1 minute

DI terminal to CX1000/CX2000 earth terminal

||

Leakage current of 2 mA or less at 0.5 kV AC for 1 minute

* Short mA, PULS, and C.

† Short NO, NC, and C.

‡ Short NO and C.

§ Short DO3—6 and C.