Data acquisition conditions, Data acquisition conditions -5, Index – Yokogawa DAQWORX User Manual

Page 16: Data acquston condtons

Advertising
background image

2-5

IM WX1-07E

1

2

3

Index

Operat

ng

Note

• If you connect to an unsupported devices, “Unknown” is displayed for the model.

• It is not supported in the UP55A’s remote-mode operation. If the operation mode is

REMOTE, it is handled as LOCAL.

• If the result, model name, control mode, control output or option functions found by

automatic model determination differ, the tag list in the tag settings dialog box is initialized.

If the tag list was modified from the initial condition, the message, “OK to initialize tag list?”

is displayed. Click the Yes button to implement the search results and initialize the tag list.

Click the Cancel button to quit without applying the results of automatic model determination

to the model settings page.

・ The automatic model determination function registers the UT55A as the UT551, the UT52A

as the UT520, the UT35A as the UT351, the UT32A as the UT321, UP55A as the UP550

and the UM33A as the UM331. The position proportional type UT35A, UT32A, UP55A and

UP35A are registered as the standard type UT351, UT321, UP550 and UP35A, respectively.

Heating / cooling type UT52A are registered as the Heating / cooling type UT551.

From the above, the one actually connected may differ from the one displayed on screen, as

follows.

 Dsplayed

 Actually connected model

 UT551

 UT55A, UT52A

 UT520

 UT52A

 UT351

 UT35A

 UT321

 UT32A

 UP550

 UP55A

 UM331

 UM33A

Data Acquston Condtons

Procedure

1.

Click the Scan Interval Settng tab or choose Vew > Scan Interval Settng from

the menu bar.

2.

Set the scan interval, access timeout, retray use, and retry interval.

Scan interval:

0.5–60 s (or 500–60000 ms: initial value is 1000 ms)

Access timeout:

1–10 sec (or 1000–10000 ms: initial value is 5000 ms)

Retry Use:

Select whether or not to retry communications (ON/OFF).

Retry interval:

The interval between communication retries (30–3600 sec).

Note

• Retries are performed every scan interval at the specified retry interval until communication

is restored. Retries are also performed on instruments with which a communication error

occurred during the first communication. At the point that communication is restored, alarm

values and other information are retrieved from the connected temperature controllers or

signal conditioners and data is acquired.

• If Retry is turned OFF, you can retry the connection manually by clicking the Retry

Connection button on the Monitor/Status tab.

2.2 Enterng Envronment Settngs