The default tag list in the Tag Settings dialog box that is displayed when you click the

detail settings in the Model Settings tab determines the model, control mode, control

output, and option function contents of the Model Settings tab.

The following describes the meanings of each tag that may appear in the Tag Settings

dialog box.

Also, the tag names listed here are reserved. Arbitrarily added tags cannot be used.

Tag Name

Meanng

PV1

Measurement input value on loop 1, or the measurement input value. The
error status and alarm status of PV1 or the measurement input value is
added.

(See section 3.3 for information on handling error and alarm statuses.)

PV2

Measurement input value on loop 2. The error status and alarm status of PV2
is added.

SP1

Target setting value used on loop 1. SP1 related alarm statuses are added.

SP2

Target setting value used on loop 2. SP2 related alarm statuses are added.

OUT1

Control output value on loop 1. Control output value on loop 1. OUT1 related
alarm statuses are added.

OUT2

Control output value on loop 2. Control output value on loop 2. OUT2 related
alarm statuses are added.

HOUT1

For heating/cooling control on loop 1, or the control output value for heating.
HOUT1 related alarm statuses are added.

HOUT2

For heating/cooling control on loop 2, or the control output value for heating.
HOUT2 related alarm statuses are added.

COUT1

For heating/cooling control on loop 1, or the control output value for cooling.
COUT1 related alarm statuses are added.

COUT2

For heating/cooling control on loop 2, or the control output value for cooling.
COUT2 related alarm statuses are added.

A/M1

Auto/manual mode for loop 1

0: AUTO (automatic) mode, 1: MAN (manual) mode

A/M2

Auto/manual mode for loop 2

0: AUTO (automatic) mode, 1: MAN (manual) mode

C.A.M

Switch between manual/automatic/cascade

0: AUTO (automatic) mode, 1: MAN (manual) mode, 2: CAS (cascade) mode

R/L1

Remote/local mode on loop 1.

0: Local, 1: Remote

R/L2

Remote/local mode on loop 2.

0: Local, 1: Remote

SPNO

Target setting value number currently used

PIDNO1

PID number used on loop 1

PIDNO2

PID number used on loop 2

R/S

Running/Stopped status

0: Running, 1: Stopped

R/P/L

Program run reset/program mode

0: Program operation reset, 1: Program operation, 2: Local operation

R/P1/P2

Program run reset/program mode

1: Program operation reset, 2: Program 1 operation, 3: Program 2 operation

HOLD

Program operation pause mode

0: Program operation, 1: Program operation pause

PVEx

PV event status. x is the event number

0: Event OFF, 1: Event ON

TMEx

Time event status. x is the event number

0: Event OFF, 1: Event ON

PTNO

Number of currently operating program pattern

SEGNO

Number of currently operating segment