Setting Data Collection Conditions
a Data time
Timestamps are attached to data that GA10 collects

from devices. You can set the type of timestamp to use

to

Device time or PC time. Device time is the time

information that the data collection device uses. PC time

is the time information that the PC in which the server is

installed uses.

• If Device time is selected

By selecting Device time, you can synchronize the

data in GA10 with the data in the corresponding

device.

In addition, the backfill function becomes available.

However, if data is collected from multiple devices,

time offset can occur between the devices and

the collection interval may be different. In other

words, data cannot be collected simultaneously with

synchronized timestamps.

What is the backfill function:

page 7-4

Note

Data collection using device time has the following

limitations.

• You cannot specify the data collection and record

interval on GA10. The interval of each device is used.

• If different acquisition intervals are used during

recording in different devices or even within the same

device, the collected data will be saved to separate

files according to the intervals.

• The trend monitor on the Monitor Page displays data

based on a single time axis. Therefore, if there are

multiple devices whose time or interval is different in

a display group, the Monitor Set will be divided and

waveforms in the display group will be displayed in

windows divided at the interval level. Only up to four

divided windows can be displayed. Anything in excess

will not be displayed.

• A similar behavior will also occur in alarm lists. The

page will be divided, and the lists will be displayed

separately at the device level. If there are multiple

acquisition intervals in the same device, the page will

not be divided at the interval level but at the device

level.

• If PC time is selected

If PC time is selected, data will be created using

synchronized timestamps. You can specify the data

collection interval and record interval, and save data

to a single data file during recording. There are no

display limitations on the Monitor Page.

Note

• Data collected using PC time will not necessarily be

the same as those of the corresponding devices:

Q9

• The timestamps attached to data in PC time mode are

determined so that data collection would always occur

at 0:00 am (00:00:00).

b Monitor Interval
Click the arrow, and select from the following intervals.

If Data time is set to Device time, you cannot specify the

Scan Interval.

Interval: 100 ms, 200 ms, 500 ms, 1 s, 2 s, 5 s, 10 s,

20 s, 30 s, 1 min, 2 min, 5 min, 10 min

c Pre-set mark
Specify text strings to assign to marks if you want to add

marks on the Trend Monitor Page.

You can assign up to 32 characters to each mark. You can

register up to five marks.

When you register text strings here, they appear in a list

on the Monitor Page as shown below, allowing you to

easily add marks.

they appear in the mark list on the Monitor Page.

When you register text strings here,

Configuring the Monitor Page
The GA10 Monitor Page can display four types of displays

(referred to as Monitor Sets): trend, digital, meter, and

alarm. A total of up to 16 Monitor Sets can be arranged on

the Monitor Page.

To display multiple Monitor Sets simultaneously, specify

how to divide the page and where to arrange each Monitor

Set.

When you specify items d to g below, a display layout

appears in the Monitor Set Layout area. By dragging the

splitters that appear between rows and columns when you

move the pointer over the boundaries, you can adjust the

size of Monitor Sets.
d Monitor Set Number

Select a number between 1 and 16.

e Splitting Direction of Monitor Set

Set the direction to arrange the Monitor Sets to

Horizontal or Vertical.

f Set Number in Splitting Direction

Select a number between 1 and 16. Options that

exceeds the Monitor Set Number are not displayed.

g Monitor Set Type

Assign Trend, Digital, Meter, or Alarm to each

Monitor Set.

Chapter 3 Configuring and Starting Data Collection and Recording