Boltek Lightning/2000 User Manual
Page 79
R E A L - T I M E L I G H T N I N G D E T E C T I O N
79
79
79
79
Default yellow alert trigger level: 25 
Default red alert trigger level: 50 
Record kept: No 
The stroke rate change counter shows the percentage 
change in the stroke rate between one minute ago 
and now. 
For example, if the stroke rate one minute ago was 
100 and the stroke rate now is 120, then the counter 
would read “+20%”; if the stroke rate one minute ago 
was 120, and the stroke rate now is 100, then the 
counter would read “-17%”. 
If the stroke rate one minute ago was zero, and the 
current stroke rate is zero, "--" is displayed. If the 
stroke rate one minute ago was zero, and the current 
stroke rate is non-zero, "*" is displayed. 
Sudden changes in the stroke rate for a storm could 
be signs that the storm is exhibiting potentially 
dangerous behavior. A rapid increase in stroke rate 
followed immediately by a rapid decrease, or vice 
versa 
has
been
linked
to
certain
severe
characteristics, such as hail, microbursts, and even 
tornadoes. 
When you specify a trigger level for the red or yellow 
alert, you are specifying the percentage change that 
must occur if the stroke rate is 100 strokes per 
minute. The percentage change that is needed for 
alert status at higher stroke rates is somewhat lower, 
and the percentage change that is needed for alert 
status at lower stroke rates is higher. 
At 1000 strokes per minute, the percentage change 
required for an alert is one-half the value specified as 
the trigger level. At 10 strokes per minute, the