Weight and physical dimensions, Facility requirements – Brocade VDX 6740 Hardware Reference Manual (Supporting VDX 6740, VDX 6740T, and VDX 6740T-1G) User Manual

Page 58

Advertising
background image

46

Brocade VDX 6740 Hardware Reference Manual

53_1002829_02

Weight and physical dimensions

A

Weight and physical dimensions

Table 10

lists the weight and dimensions of the Brocade VDX 6740 switches.

Facility requirements

Table 11

provides the facilities requirements that must be met for the Brocade VDX 6740.

TABLE 10

Physical specifications

Dimension

Value

Height

44.45 mm (1.75 in.) - Brocade VDX 6740
42.67 mm (1.68 in.) - Brocade VDX 6740T and Brocade
VDX 6740T-1G

Depth

409.16 mm (16.14 in.) - Brocade VDX 6740
536.45 mm (21.12 in.) - Brocade VDX 6740T and
Brocade VDX 6740T-1G

Width

439.93 mm (17.32 in.) - Brocade VDX 6740
437.38 mm (17.22 in.) - Brocade VDX 6740T and
Brocade VDX 6740T-1G

Weight (with all power supplies and fan assemblies, and
no transceivers installed)

8.66 kg (19.10 lb) - Brocade VDX 6740
10.82 kg (23.85 lb) - Brocade VDX 6740T and Brocade
VDX 6740T-1G

TABLE 11

Facility requirements

Type

Requirements

Electrical

Primary AC input rated 100-240 VAC, operating input range 90-264 VAC (Brocade VDX
6740), 85-264 VAC (Brocade VDX 6740T), 50-60 Hz; switch autosenses input voltage

Adequate supply circuit, line fusing, and wire size, as specified by the electrical rating
on the switch nameplate

Circuit protected by a circuit breaker and grounded in accordance with local electrical
codes

Refer to

Table 12 on page 47

for complete power supply specifications.

Thermal

Ambient air temperature not exceeding 40

C (104

F) while the switch is operating

Rack

One rack unit (1U) in a 48.3 cm (19-inch) rack - Brocade VDX 6740

All equipment in cabinet grounded through a reliable branch circuit connection

Additional weight of switch not to exceed the rack’s weight limits

Rack secured to ensure stability in case of unexpected movement