Installation, Technical specifications – dc655e (ce) – Lincoln Electric IM983 RED-D-ARC DC655e (CE) User Manual
Page 10
![background image](/manuals/363654/10/background.png)
A-1
DC655e (CE) (RED-D-ARC)
A-1
INSTALLATION
TECHNICAL SPECIFICATIONS – DC655e (CE)
Volts at Rated Amperes
44
44
Auxiliary Power
See the OPERATION section for
Auxiliary Power information
Amps
650
815
Maximum Open Circuit Voltage
46 CV Mode
68 CC Mode
Duty Cycle
100% Duty Cycle
IEC974-1
60% Duty Cycle
INPUT - THREE PHASE ONLY
OUTPUT
1Also called “inverse time” or “thermal/magnetic” circuit breakers; circuit breakers which have a delay in tripping action that decreases as the magnitude of the current increases.
RECOMMENDED INPUT WIRE AND FUSE SIZES
Standard
Voltage
230/400/50/60*
100% Duty Cycle
122/70
60% Duty Cycle
150/86
Input Current at Rated Output
RATED OUTPUT
INPUT
VOLTAGE /
FREQUENCY
230
400
(SUPER LAG)
OR BREAKER
SIZE (AMPS)
1
225 Amp
125 Amp
Copper
GROUND WIRE
IN CONDUIT
AWG(IEC-MM
2
) SIZES
4 (21)
6 (14)
TYPE 80°C
COPPER WIRE
IN CONDUIT
AWG(IEC-MM
2
) SIZES
40°C (104°F) Ambient
1 (43)
4 (21)
INPUT AMPERE
RATING ON
NAMEPLATE
122
70
HERTZ
50/60
50/60
PHYSICAL DIMENSIONS
HEIGHT
27.5 in
699 mm
WIDTH
22.2 in
564 mm
DEPTH
38.0 in
965 mm
WEIGHT
720 lbs.
326 kg.
Current Range
50-815
Voltage Range
13-44 DC