Van Air Systems High Dew Point Alarm Box User Manual

High dew point alarm box

Advertising
background image

PAGE 1

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

FOR

HIGH DEW POINT ALARM BOX

P/N 46-2064

SPECIFICATIONS AND DIMENSIONS

SECTION 1

WEIGHT ................ 25 LBS
DIMENSIONS ........ see Figure 2A
MOUNTING .......... see Figure 2A

ENCLOSURE

• Enamel painted Steel Enclosure
• Nema 4 Rated
• Continuous Hinged

DEW POINT CONTROLLER (humistat)

RANGE OF CONTROL ................... 4% to 98% Relative Humidity

(NOTE: Set plug and sensor determine actual operating range)

INPUT POWER ................................. 115V-1PH-56/60Hz
OUTPUT MODE ............................... SPDT. relay, 1 amperes,
noninductive maximum

DEW POINT SENSOR (hygrosensor)

RANGE OF CONTROL ................... 1.4% to 6% RH @ 80

o

F

TYPE ................................................. DUNMORE-TYPE lithium
chloride element.

SET POINT PLUG

SET POINT ....................................... approx. 0

O

F Dew point @ 80

o

F

DEW POINT SAMPLE CELL

• Sample line isolation needle valve
• Sample cell bleed orifice fitting
MAXIMUM SAMPLE AIR PRESSURE ............. 150 PSIG
SAMPLE LINE CONNECTION SIZE ............... 1/4" tube fitting

ALARM OUTPUT CONTACT

ELECTRICAL RATING .................... 115V-1PH-60Hz, 10 ampere
OUTPUT MODE ............................... Normally open contact,
latching (push-button must be pressed to reset)

LIGHT & RESET PUSH-BUTTON

• High Dew Point Light (red)
• Alarm Reset Push-button

FEBRUARY 2006

32-0283