MAINTENANCE

SECTION 5

5.4 HUMISTAT CALIBRATION PROCEDURES

After the sampling line and power lines are connected, the humistat
must be adjusted as follows:

Unplug the cable from the dew point sensor.

Plug the set plug into the cable.

Apply power to the controller and adjust the potentiometer,
(REFERENCE FIGURE 5A), on the PC board. Rotate the
potentiometer back and forth, noting the position of the screw-
driver slot when the relay clicks as it pulls in and drops out. Set
the potentiometer midway between these two points.

Remove the set plug.

Plug the cable back to the dew point sensor.

The humistat is now ready for operation.

FIGURE 5A HUMISTAT DETAIL

REPLACEMENT PARTS

SECTION 6

ITEM NO

DESCRIPTION

PART NO

QTY

1

ISOLATION VALVE

14-1306

1

2

BLEED ORIFICE

26-0490

1

3

DEW POINT SENSOR

26-0817

1

4

SENSOR MOUNT

26-0816

1

5

CABLE

46-2185

1

6

HUMISTAT

26-0814

1

7

SET PLUG

26-0818

1

8

REPLACEMENT LIGHT BULB

26-0726

1

9

LIGHT ASSEMBLY (W/RED LENS)

26-2141

1

10

RESET PUSHBUTTON

26-3757

1

11

ORIFICE COUPLING

26-0657

1

12

ORIFICE BUSHING

26-0296

1

13

CONTROL RELAY

26-0813

1

14

MUFFLER

26-0623

1

2950 Mechanic Street

Lake City, PA 16423 USA

Phone: 800/840-9906

Corporate Fax: 814/774-0778

Order Entry Fax: 814/774-3482

www.vanairsystems.com

-5&&,%2

/2)&)#%

!.$

",%%$

3%.3/2

3!-0,%

)3/,!4)/.

/ 2).'

3%.3/2

#!",%

(5-)34!4

3%4

0/4%.4)/-%4%2

Advertising