Host PC

5.7

CONFIGURATION FILE

The system configuration file is a text file named CatHostDir.txt. It is
located in the application folder and appears as the following:

\Data

Start-up Period(Hours),.25

Maximum Interval Between

Communications(Minutes),20

Minimum Time Between Alerts(Minutes), 2

Early Off Start Time,7

Early Off End Time,16

Early Off Diferential,.5

Comm Port,5

Comm Port2,0

• The first record is always \Data
• The Start-up Period is the amount of time after the program starts

before any control action takes place. This time is necessary to
allow all the buoys to transmit at least one reading to the host.

Maximum Interval Between Communications is the maximum

time allowed between receipts of readings from a buoy. If this time
is exceeded, it is assumed that communications between the buoy
and the host have failed. The current oxygen reading on the screen
will be changed to a red zero to indicate this failure.

Minimum Time Between Alerts is not used.
Early Off Start Time is the hour after which the early off differential

will be applied. A time of 7 will cause the differential to be applied
after 8 am.

Early Off End Time is the hour after which the differential will be

removed.

Early Off Differential is the adjustment amount for the early off

feature. This is the amount that will be subtracted from the normal
on/off levels between the Early Off Start Time and the Early Off End
Time.

Comm Port is the communications port number.
Comm Port2 is the communications port number if two ports are

used. If only one port is used the value will be zero.

5.8

SET PHONE ALERTS

The Set Phone Alerts window is used to set all alerts.

1. On the main menu of the Pond Status screen, select Set Phone

Alerts.

2. Select the pond to be set. The current minimum aerator amperage

settings and minimum oxygen levels will appear. If an amperage
reading or oxygen reading is returned that is below the minimum,
an alert will appear on the Farm Status screen and a telephone alert
will be sent.