Electrical connections, 4 networks, 1 general information – KROHNE OPTIWAVE 6300C EN User Manual

Page 33: 2 point-to-point connection

Advertising
background image

ELECTRICAL CONNECTIONS

4

33

OPTIWAVE 6300 C

www.krohne.com

03/2014 - 4000547004 - HB OPTIWAVE 6300 R04 en

4.4 Networks

4.4.1 General information

The device uses the HART

®

communication protocol. This protocol agrees with the HART

®

Communication Foundation standard. The device can be connected point-to-point. It can also
operate in a multi-drop network of up to 15 devices.

The device output is factory-set to communicate point-to-point. To change the communication
mode from point-to-point

point-to-point

point-to-point

point-to-point to multi-drop

multi-drop

multi-drop

multi-drop, refer to

Network configuration

on page 57.

4.4.2 Point-to-point connection

Figure 4-4: Point-to-point connection (non-Ex)

1 Address of the device (0 for point-to-point connection)
2 4...20 mA + HART

®

3 Resistor for HART

®

communication

4 Power supply
5 HART

®

converter

6 HART

®

communication software