Operation – KROHNE OPTIWAVE 6300C EN User Manual

Page 55

Advertising
background image

OPERATION

6

55

OPTIWAVE 6300 C

www.krohne.com

03/2014 - 4000547004 - HB OPTIWAVE 6300 R04 en

C.3.4

Output Range

Sets the effective range of output 1

either with or without over-run.

min.-max: 3.8…20.5 mA

(NAMUR), 4…20 mA

4…20 mA

C.3.5

Error Handling

This sets the behaviour of current

output 1 if an error occurs. Hold means

that the output current stays at the

value where the error occurred. Hold is

not available if 3.8…20.5 mA (NAMUR)

is the output range.

3.6 mA, 22 mA, Hold

22 mA

Error Handling

Delay

The time after which the current output

changes to an error value. It shows

that there is a measurement error.

min.-max:

0…900 sec (seconds)

10 sec

C.3.6

HART Address

Any HART

®

address greater than 0 will

activate HART

®

multidrop mode. The

current output stays constant at 4 mA.

min.-max: 0…15

0

C.4 Output 2 (Passive)

C.4.1

Output

Function

Select an output function to scale the

current values. This is not displayed in

the operator mode.

Level, Distance, Volume

(Mass), Ullage Volume (Ullage

Mass), Reflection

Level

C.4.2

4 mA Setting

Give a measurement value to 4 mA.

min.-max:

1

0 m / 0 ft

C.4.3

20 mA Setting

Give a measurement value to 20 mA.

min.-max:

2

Depends on the

output function

C.4.4

Output Range

Sets the effective range of output 2

either with or without over-run.

min.-max: 3.8…20.5 mA

(NAMUR), 4…20 mA

4…20 mA

C.4.5

Error Handling

This sets the behaviour of current

output 2 if an error occurs. Hold means

that the output current stays at the

value where the error occurred. Hold is

not available if 3.8…20.5 mA (NAMUR)

is the output range.

3.6 mA, 22 mA, Hold

22 mA

Error Handling

Delay

The time after which the device shows

there is a measurement error. This

value is set in the output 1 menu.

Read only

Refer to

function C.3.5

C.5 Device Setup

C.5.1

C.5.1

C.5.1

C.5.1

Display

Display

Display

Display

Settings

Settings

Settings

Settings

To display the information you need,

To display the information you need,

To display the information you need,

To display the information you need,

refer to these menu items.

refer to these menu items.

refer to these menu items.

refer to these menu items.

C.5.1.1

Language

Information can be displayed in any of

the 9 languages stored in the device. If

it is necessary to change the display

quickly to English, push [







] for 3

seconds in operator mode.

English, French, German,

Italian, Japanese, Chinese

(simplified), Portuguese,

Russian, Spanish

C.5.1.2

Display Mode

The display screen status will change

after the time given in C.5.1.3. (time

delay). Disable

Disable

Disable

Disable switches off this

functionality, Auto-Off

Auto-Off

Auto-Off

Auto-Off switches off the

display and Default Screen

Default Screen

Default Screen

Default Screen will show

the selected default screen. To set to

the default screen, push [







] for 1

second in the operator mode.

Disable, Auto-Off, Default

Screen

Disable

C.5.1.3

Time Delay

The time after which the display will

switch to the status set in C.5.1.2

(Display Mode).

1, 3, 5, 10 (minutes)

1

Contrast

The contrast control for the display

screen. You can select a shade of gray

between light gray (level 1) and black

(level 9).

Level 1, Level 2, Level 3, Level

4, Level 5, Level 6, Level 7,

Level 8, Level 9

Level 5

Menu

No.

Function

Function description

Selection list

Default

Advertising