Operation – KROHNE OPTIWAVE 6300C EN User Manual
Page 49

OPERATION
6
49
OPTIWAVE 6300 C
www.krohne.com
03/2014 - 4000547004 - HB OPTIWAVE 6300 R04 en
6
Tank Shape
The Wizard adds this step if you
select "Yes" in step 4. This sub-
procedure uses the
information given here to find
the volume. You have to type in
the tank shape, height, width
and length.
...
...
7
Conversion Unit
The conversion unit is given as
a volume if the product density
is given. If not, choose a mass
unit.
m3, L, US gal, GB gal, ft3,
bbl or Tons, kg, US Tons, GB
Tons
m3 or Tons
8
Mass Table
A table that converts product
level to product mass. If you
selected "Yes" in step 4, make
entries in the table in volume
units. Push[
] or [
] to select
a line and push [>>>>] to change
values automatically supplied
by the device.
Sub-
menu
Conversion
submenu
[Free Unit]
[Free Unit]
[Free Unit]
[Free Unit]
If you cannot find the units or
silo shape in the menu, you can
customize the conversion
table.
–
1
Do you want to use
free unit?
Select "Yes".
Yes, No
No
2
Custom. Length
Unit
A non-standard length unit for
the conversion table. This is
defined by the supervisor.
LEN_
FREE_
3
Custom. Length
Ratio
The conversion factor between
the length unit selected in
C.5.1.4 (length unit) and C.5.1.7
(customer length unit). This
ratio is a multiple of 1 mm.
min-max: 1…99999
1
4
Custom. Conv. Unit A non-standard conversion unit
for the conversion table. This is
defined by the supervisor.
CO_FR_UN
5
No. of Entries
The number of lines in the
conversion table.
min-max: 0…50
2
6
Volume/Mass
Table
A table that converts product
level to another physical
parameter. Push[
] or [
] to
select a line and push [>>>>] to
change values automatically
supplied by the device.
...
Current changes
must be saved or
cancelled before
proceeding
Save, Cancel
3
Save
A.1.5
A.1.5
A.1.5
A.1.5
Outputs
Outputs
Outputs
Outputs
Follow this procedure to
Follow this procedure to
Follow this procedure to
Follow this procedure to
describe the output
describe the output
describe the output
describe the output
characteristics.
characteristics.
characteristics.
characteristics.
1
Output 1: Output
Function
Select an output function to
scale the current values
(output 1). This is not displayed
in the operator mode.
Level, Distance, Volume
(Mass), Ullage Volume
(Ullage Mass), Reflection
Level
2
Output 1 (HART):
<Function> 4 mA
This assigns a measurement
value to 4 mA (output 1).
min-max:
0…20 m / 0…65.62 ft
0 m / 0 ft
3
Output 1 (HART):
<Function> 20 mA
This assigns a measurement
value to 20 mA (output 1).
min-max:
0…90 m / 0…295.29 ft
Depends on
the output
function
Menu
No.
Step
Function
Function description
Selection list
Default