KROHNE UFM 600T EN User Manual

Page 46

Advertising
background image

Active output

short-circuit-proof

Terminals 4.1/4.2 :

for electromechanical (EMC) or
electronic (EC) totalizers

Terminals 4/4.1/4.2:

for electronic (EC) totalizers

Amplitude

:

approx. 27 V

Load rating

see Table "pulse width"

Passive output
Terminals 4/4.1

: open collector for connection of

active electronic totalizers (EC)
or switchgear

Input voltage

: 5 to 30 V

Load current

: max. 100 mA

Pulse width is automatically choosen, depending on actual out
frequency.

Frequency f at Q=100%

Pulse width

Load rating of active output
Load current

Load

0.0028 Hz < f

1 Hz

500 ms

≤ 150 mA

≥ 180 Ohm

approx.
50% duty

1 Hz < f

≤ 10 Hz cycle (1:1)

≤ 25 mA

≥ 1 k Ohm

50% duty

10 Hz < f

≤ 1000 Hz cycle (1:1)

≤ 25 mA

≥ 1 k Ohm

1000 Hz < f

≤ 2547 Hz 160 µs

≤ 25 mA

≥ 1 k Ohm

2547 Hz < f

≤10000 Hz 50 µs

≤ 25 mA

≥ 1 k Ohm

45