KROHNE UFM 600T EN User Manual

Page 66

Advertising
background image

3.4.0 FREQ. OUTP. F

:

set up frequency /
pulse output

3.4.1 FUNCTION F

:

Program the analog fre-
quency output

Select an output option using the key and press

to store:

2 DIR

:

Enables flow measurement in 2 direc-
tions (fig. D.7).

TRAN. TIME

:

Output signal is proportional to the
measured transit time of the acoustic
signal.

NOTE:

This function requires:
- PULSRATE setting, Fct. 3.4.2
- PULSRATE at full flow, Fct. 3.4.3
- Transit time at full flow, Fct. 3.1.2
(see example in description of Fct. 3.1.2)

NO SIGNAL

:

Output signal indicates "signal loss".

OFF

:

No frequency output.

F/R IND. F

:

Output signal as flow direction indica-
tion, 0% at + flow direction and
100% at - flow direction (Fig. D.8).

1 DIR

:

Flow measurement in 1 direction (+)

only (Fig. D.9).

Fig. D.7 : Bi-directional flow(F)

Fig. D.8: Flow direction indication(F)

63

signal received

signal lost

only (Fig. D.9).

Advertising