SUMMIT 8800

CALIBRATION

08

8. Calibration

Calibration should be carried out by qualified personnel. This function allows certain available

Inputs and Outputs to be calibrated for accuracy, which is performed using the Windows con-

figuration software.

The procedure is described in the Help Menu and from the front panel of the flow computer.

Calibrate mode is entered as a sub-menu from the Edit Mode, the entry procedure is described

later in this chapter.

The I/O card to be calibrated is selected from a list of available cards in the flow computer. The

Calibrate button should then be operated. Status of the selected Card will be read and a Calibra-

tion window will appear.

The following types of different Inputs and Outputs can be Calibrated, and are selected by the

individual items in the Calibration list.

8 .1 Input Calibration

8 .1 .1 HART Input

Calibration of the HART Transmitter Inputs is performed using a Digital Handheld or other

similar calibration device supplied by the transmitter’s manufacturer. The transmitters are

connected to the flow computer in parallel as a multidrop system and as such, each transmitter

must have a different address.

It is essential that the transmitters have their addresses programmed and the burst mode op-

eration turned off before they are connected to the flow computer.

In the flow computer it is necessary to suspend HART Communication to the HART transmitters

whilst they are being calibrated. Communication on any one connection loop can be suspended

to all transmitters, or individually. The Start Communication and Stop Communication buttons

are used for this purpose.

All transmitter communication will automatically be re-started irrespective of the button status,

when the Close button is selected.