CALIBRATION
08
Main Controls:
Start Calibrate
starts the calibration process
Write
write the new calibration data to the connected flow computer
Discard
discards any calibration changes made.
Default
reverts to default factory calibration.
Stop calibrate
stops the calibration process.
Figure 93 Calibrate analog input
Adjusting the input range:
• Evaluate the field instrument data sheet and take particular note of its range setting for
minimum and maximum process values. Assume that a board arrives factory calibrated for 4
and 20mA. In below example a field temperature sensor ranges -50 to 150 degrees Celsius.
Alter the two wanted field record accordingly (as shown below). Do not click either of the SET
buttons but click the WRITE button.
Figure 94 Calibration selection screen