Electrical connections – KROHNE MFC 400 EN User Manual
Page 51

ELECTRICAL CONNECTIONS
4
51
MFC 400
www.krohne.com
08/2013 - 4002075802 - MA MFC 400 R02 en
4.10.5 Ex i inputs/outputs
Current output active (only current output terminals C/C- have HART
®
capability), Ex i
I/Os
• Observe connection polarity.
• U
int, nom
= 20 VDC
• I ≤ 22 mA
• R
L
≤ 450 Ω
• X designates the connection terminals A or C, depending on the version of the signal
converter.
Current output passive (only current output terminals C/C- have HART
®
capability),
Ex i I/Os
• Any connection polarity.
• U
ext
≤ 32 VDC
• I ≤ 22 mA
• U
0
≥ 4 V
• R
L
≤ (U
ext
- U
0
) / I
max
• X designates the connection terminals A or C, depending on the version of the signal
converter.
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
INFORMATION!
For further information on electrical connection refer to Description of the inputs and outputs on
page 38.