Instantaneous value measurement: w range, 1. steps for measurement – KYORITSU 6305 Quick Manual User Manual

Page 15

Advertising
background image

−

14 −

KEW6305

KEW6305

Instantaneous value Measurement:

W

Range

6. Instantaneous value Measurement:

W

Range

6-1. Steps for measurement

Ensuring your safety

↓

Preparation for measurement

↓

Setting

↓

Wiring

↓

Instantaneous value measurement

●

Parameters for

W

Range

Parameters to be displayed on the LCD

Unit

Voltage

(RMS)

V

: average voltage of each phase

Vi

: voltage of each phase

V

Current

(RMS)

A

: average current of each phase

Ai

: current of each phase

A

Active

power

P

: total active power

Pi : active power of each phase

Polarity :+ (no sign) consumption

- (minus) regenerating

W

Reactive

power

Q

: total reactive power

Qi : reactive power of each phase

Polarity :+ (no sign) lagging phase

- (minus) leading phase

Var

Apparent

power S

: total apparent power Si: apparent power of each phase

VA

Power

factor

PF

: power factor of whole system

PFi : power factor of each phase

Polarity :+ (no sign) lagging phase

- (minus) leading phase

PF

Frequency f

: frequency of V1

Hz

Neutral

current In

: current on neutral line (3P4W only)

An

* i = 1, 2, 3    

SET UP Range

Basic setting

Measurement setting

“

Setting 01” Wiring system

“

Setting 02” Voltage range

“

Setting 03” Clamp sensor

“

Setting 04” Current range

“

Setting 05” VT ratio (if necessary)

“

Setting 06” CT ratio (if necessary)

Range

Advertising