NSi Industries DGLC Old Series User Manual

Page 3

Advertising
background image

at 1 to 2 footcandles. If adjusted to the extreme
right (MAX position), the ON relay will close at
approximately 100 footcandles. (There is a 2 - 4
second built-in delay).

IMPORTANT: The potentiometer allows you to
adjust a turn ON at 1 to 100 footcandles. OFF will
be 3 times the ratio of the ON foot candle level.
Light level adjustment is the same for both
circuits.

IMPORTANT NOTES CONCERNING THE
PHOTOCELL INPUT:

1. An ON event must be scheduled prior to sun-

set in order for the photocell to activate circuit
#1. Timer can then be scheduled OFF and
later ON again before sunrise for any desired
days.

2. Circuit #2 is directly controlled by photocell

and light level adjustment. It is not governed
by timer or the manual override.

3. Photocell can be wired up to 500 feet from

timer using 2 wire, #18 to #22 AWG, between
input terminal and photocell.

4. Do not put excessive pressure on potentiome-

ter. Use thumb and forefinger or small screw-
driver to adjust for light level. Avoid shorting
screwdriver to upper board.

5. Light level adjustment operates only with Tork

Photocell Model EPC1.

KEY FUNCTIONS

DAY/MONTH: Press to advance the day in the
CLK mode. Press to advance the Month in the
DATE mode.

HOUR/DATE: Press to set the Hours in the CLK
mode and in the Schedule SET mode. Press to
advance Date in the DATE mode.

3

LIGHT LEVEL ADJ.

MIN

MAX

DAY

MONTH

HOUR

DATE

MIN

YEAR

OVER-

RIDE

MODE

SP DAY

ON/OFF

ENTER

MIN/YEAR: Press to set the Minute in the CLK
mode and in the Schedule SET mode. Press to
advance Year in the DATE mode.

OVERRIDE: Press to alter the Load status and/or
to Override scheduled event on circuit #1 only.

MODE: Press to advance to next mode without
affecting the scheduled memory information.
Sequence is: RUN, CLK, DATE, schedule SET. In
the SET mode, unit automatically reverts to
the RUN mode if no entries are made for 5
minutes.

SP DAY: Press during RUN mode to execute the
“SPECIAL DAY’ schedule everyday. LCD will dis-
play D in upper right corner. Pressing SP DAY
again will toggle the unit back to normal 7 day
program operation.

ON/OFF: Pressing each time will select an ON or
an OFF. Multiple OFF’s may be scheduled to can-
cel override ON’s.

ENTER: Press to store the displayed information
into memory. Information will not be stored
until ENTER is pressed.

NOTE: During settings, each press of the key will
advance one number. For rapid advance, hold
key in.

SELECT AM/PM OR 24 HOUR

MILITARY FORMAT:

Upon powering up the unit the LCD will display
the model number 100. The LCD will next display
12H which is an automatic (AM/PM) format.

Press ENTER to keep AM/PM format or press
HOUR key to alter to 24 hour (Military) format and
then press ENTER.

4