exceed the length shown in the chart above . Calibrate

per instructions below .

The other terminal block, TB2 is used as remote

override inputs . Three wires are used: common

wire, channel 2 (if DGLC200A), and channel 1 .

NOTE: Do not use any supply voltage for these wires .

They should only be connected to dry (unpowered)

switches . Closing contacts between the wires for

channel 1 and common together will turn load 1 ON .

Load will stay ON as long as the two wires are

connected, no matter what the timer is set for, or the

light level . Closing contacts between the wires for

channel 2 and common together will turn load 2 ON .

The load status change due to remote override will not

be shown in the display .

Photo Sensor Calibration

After installation, in order to ensure accurate light level

performance, completely cover the EPC-A sensor .

Then gently press the recessed Sensor CAL Switch

for at least 5 seconds . After this button has been

pressed, the red LED directly above the button will

blink four times . If the button is pressed accidentally

when the light level is above 10 foot candles, the unit

will not recalibrate and the LED will blink once to signal

that it did not change calibration .