E500t, On delay timer, Installation & wiring instructions – NSi Industries E500T User Manual

Page 3

Advertising
background image

MODEL#:

E500T

The E500T is an ON delay timer which allows for a set time interval to elapse before the load connected to the timer is powered ON. An external maintained contact switch (by others) is used to start the

delay time. Once turned ON, the load will remain on until the external switch is opened.
It has an adjustable rotary dial which contains 32 precisely defined positions, allowing for interval durations from five (5) seconds minimum to 3 hours maximum. Continuous ON and continuous OFF

settings are included.

POwEr

rEquirEMEnts:

Input: 120 and 240 VAC (+10% -15% at 60 Hz).

Outputs: SPDT relay with 20 Amp N.O. and 10 Amp N.C. general purpose at 120,240 VAC; N.O. 1 HP at 120 VAC, 2HP at 240 VAC

EnvirOnMEntaL: Operating Temperature Range: 32°F to 122°F (0°C to 50°C). Operating Humidity Range: Relative humidity up to 100%

Water Resistance: The control will be capable of direct low-pressure water wash down according to NEMA 4X specification.

COntaCt

ratinG:

EnCLOsurE:

NEMA type 4X (indoor use only) enclosure standard (E500T). Watertight cover with gasket - flame retardant UV stabilized & non-metallic. In grey.

MOuntinG:

Control is compatible for mounting to Tork’s NEMA 4X nonmetallic enclosure.

DiaLs:

Sealed from external access

MaintEnanCE:

Cleaning: Use only mild detergent and water to dean the enclosure

INSTALLATION & WIRING INSTRUCTIONS

Note: Wiring connections are made to a six-position: terminal block.

All terminals accept AWG #18 to AWG #12 wire.

1. Turn off all power to the timer circuit at the distribution panel before

beginning the installation.

2. The E500T box contains knockouts on two sides. Determine the most

convenient way to mount the box to the conduit and remove the appropri-

ate knockout. To secure the box to a fixed location, use at least two of the

four box mounting knockouts located on the back of the box.

3. Wire timer for either 120 VAC or 240 VAC as shown by the wiring dia-

gram. Wire the load to the timer as shown in the wiring diagram, noting

the contact load type and ratings shown.

4. Connect external trigger contacts to the timer as shown in the wiring

diagram.

5. Securely attach the timer to Tork’s NEMA 4X (for indoor use only) non-

metallic enclosure with the included screws

®

ON DELAY TIMER

VOLTAGE

LOAD TYPE

N.O. CONTACTS

N.C. CONTACTS

120-240 VAC

Resistive

20 A

10 A

120-240 VAC

General Purpose

20 A

10 A

120 VAC

Motor

1 HP

¼ HP

208-240 VAC

Motor

2 HP

½ HP

120-240 VAC

Pilot Duty

470 VA

275 VA

TRIGGER

T

LOAD

START

NC

NO

COM

240V/L1

120V NEUT/L2

120V

L

N

FOR 240V

L2

L1

EXTERNAL

TRIGGER

(CONTACTS)

SPDT

120V

L

N

L1

L2

FOR 240V

APPLY ONLY ONE VOLTAGE

FOR 120V

(L)

FOR 240V

(L1)

! CAUTION !

RISK OF ELECTRIC ShOCK

Disconnect power at main panel prior to installing

or servicing this lighting control or the equipment connected to it.