APPLICATION NOTES

TYPICAL INTERFACE WITH TORK CONTACTORS

Model 5401 - DPST
To control 120 volt circuits where increased voltage and/or
amperage switching is necessary, close or remote from controller.
Can switch up to 40 amps per pole from 120VAC to 480VAC —
one or two circuits simultaneously. Indoor-outdoor enclosure.

TYPICAL INTERFACE WITH

MOMENTARY CONTACT ADAPTER

Model SMC-3D
Momentary contact adapter 120V input maintained contact
converts to SPDT pulsed (2 seconds) circuits. Pulsed switching
circuit will control 24VAC up to 277VAC.

TYPICAL INTERFACE WITH DAY/NIGHT THERMOSTAT

A typical wiring diagram of how to use the Z400B for night set-back
for heating or night set-up for cooling.

Winter Set-back: Set 2-wire night thermostat at 55°F. When
control is “OFF” temperature will not go below 55°.

When control is “ON” (day hours) day thermostat set at 70° to 72°
will override night thermostat.

Summer Set-up: Night thermostat is usually set at 90° to 95°.
When control turns “ON”, day thermostat will override night setting
and cool to (76° to 78°) day setting.

REMOTE TIMED OVERRIDES

8

TORK MODEL Z400B TERMINAL BLOCK

NO

C

NC

OPEN

CLOSE

C

120 VAC

LINE

NEUTRAL

120 VAC COIL

TORK MODELS 5401 & 5441
OR SUITABLE SUBSTITUTE

LOAD

Electrically-
held contactor

Mechanically-
held contactor
self clearing

120/240V LINE
277/480V
40 AMP/POLE

TORK MODEL Z400B TERMINAL BLOCK

NO

C

NC

POWER

24 VOLTS

LOW VOLTAGE

CONTROL POWER
FROM HVAC UNIT

24 Volts
Two Wire
Night
Thermostat
(Time Switch
Circuit OFF)

Day Thermostat

4-Wire Heat/Cool Thermostat

(Time Switch Circuit ON)

HEAT

COOL

FAN

WHITE

YELLOW

GREEN

RED

TORK MODEL Z400B TERMINAL BLOCK

NC

OPEN

ON

120/240

VAC

SURGE

SUPPRESSOR

LINE

NEUTRAL

120 VAC

TO

CONTACTOR

LINE

OFF

Tork Model SMC-3

CLOSE

24 - 277VAC LINE

COMMON

ON

OFF

REMOTE

MANUAL
STATION

N

LINE

NO

C

TORK DIGITAL TERMINAL BLOCK

NO

C

NC

120V 60HZ

LINE

NEUTRAL

120V
COIL

5401

CONTACTOR

LIGHTING

LOAD

120/240V
277/480V
40 AMPS

PER POLE

TORK DIGITAL TERMINAL BLOCK

NO

C

NC

Load to Security

and Alarm System

Load from Security

and Alarm System

TORK MODEL Z400B TERMINAL BLOCK

1

COMMON

MOMENTARY PUSHBUTTON

2

3

4