AUTOTUNE (continued)

TUNE OR TUNE AT SETPOINT PROGRAM

Enter program (▲▼) and from the display

tunE : oFF

press and hold ✱ and press ▲ to

display

tunE : on

or

tunE : At.SP

Exit program mode (▲▼).

The

TUNE

program will now start. The display will show

tunE

as the process variable

climbs to setpoint.

Note: Avoid tuning while running a program as SP1 may be different from the target

setpoint..

When the

TUNE

or

TUNE AT SETPOINT

program is complete the PID values are entered

automatically. The process will rise to setpoint and control should be stable. If not, this may
be because optimum cycle time is not automatically implemented. To set the cycle time
see PROPORTIONAL CYCLE-TIME.

PROPORTIONAL CYCLE-TIME

The choice of cycle-time is influenced by the external switching device or load. eg.
contactor, SSR, valve. A setting that is too long for the process will cause oscillation and a
setting that is too short will cause unnecessary wear to an electro-mechanical switching
device.

Factory set
To use the 20 sec factory set cycle-time no action is needed whether autotune is used or
not.

To Manually Select AUTOTUNE Calculated CYCLE-TIME
When AUTOTUNE is completed, enter program (▲▼) and select

CYC.t

in Level 1. The

display will read

CYC.t : 20

(the factory setting).

To view the new calculated optimum value, press and hold both ✱ and ▼ buttons until
indexing stops. The calculated value will be displayed eg.

A16

. If acceptable, exit program

(▲▼) to implement this setting.

To Pre-select Automatic Acceptance of AUTOTUNE Calculated CYCLE-TIME
Before AUTOTUNE is initiated select

CYC.t

in Level1, press and hold both ✱ and ▼ buttons

until indexing stops at

A – –

. Exit program (▲▼) to accept calculated value automatically.

To Manually Pre-select Preferred CYCLE-TIME
Before AUTOTUNE is initiated select

CYC.t

in Level 1, press and hold both ✱ and ▲ or ▼

buttons until indexing stops at preferred value then exit program (▲▼) to accept.

CYCLE-TIME RECOMMENDATIONS

SECOND AND THIRD SETPOINTS

(SP2 and SP3)

PRIMARY ALARM MODES

Configure SP2 output to operate as an alarm from

SP2.A

in Level 2 and set the alarm

setting in

SEt.2

Level 1.

Configure SP3 alarm mode

SP3.A

and setting

SEt.3

in Level A. The alarms will be

individually triggered when the process value changes according to the options listed
below.

dV.hi

Rises above the main setpoint by the value inserted at

SEt.2/3.

dV.Lo

Falls below the main setpoint by the value inserted at

SEt.2/3.

BAnd

Rises above or falls below the main setpoint by the value inserted at

SEt.2/3.

FS.hi

Rises above the full scale setting of

SEt.2

or

SEt.3.

FS.Lo

Falls below the full scale setting of

SEt.2

or

SEt.3.

EoP

Event Output (See Programmer section pages 11 to 18)

SUBSIDIARY SP2 / SP3 MODES

The following additional Subsidiary alarm functions can be added to any Primary alarm
configurations using the settings found at

SP2.b

in Level 2 and

SP3.b

in Level A.

LtCh

Once activated, the alarms will latch and can be manually reset when the alarm
condition has been removed.

Hold

This feature inhibits alarm operations on power-up and is automatically disabled
once the process reaches the alarm setting.

Lt.ho

Combines the effects of both

LtCh

and

hoLd

and can be applied to any Primary

alarm configuration.

SECOND SETPOINT (SP2) Proportional control output

Configure in Level 1 using

CyC.2

to select proportional cycle time and

bnd.2

to adjust

proportioning band. For Heat/Cool operation see Operating Manual.

Additional in depth information on controller operation is available in the CAL 9400.PDF
available for down load from www.cal-controls.com

In on–off mode,

bnd.2

adjusts SP2 hysterisis.

5

Output Device

Factory Setting

Recommended Minimum

Internal relays

20 seconds

20 seconds

10 seconds

Solid state drives

0.1 seconds

Hereafter in the Manual the symbol (▲▼) signifies both buttons are held pressed

for 3 seconds to ENTER or EXIT Program mode.

Alarm type On-Off operating mode SP2 and SP3 Proportional operating mode SP2 only

FS.HI

COOL

FS.LO

BAND

DV.LO

DV.HI

Deviation

Full scale

Strategy

Output state

LED state

Output state

LED state

BAND

: on-off mode only

Output ON

(Relay or SSd

energised)

Output OFF

(Relay or SSd

de-energised)

LED ON

Temperature above setpoint

Legend

English