INPUT SELECTION AND RANGING

dI.SP [1]

0.1

Select display resolution: for display of process value, setpoint,

OFSt, Set.2, hi.SC, LoSC

.

hi.SC

[sensor maximum]

sensor maximum

°C/°F/units

Set full scale

Lo.SC

[sensor minimum]

sensor minimum

°C/ºF/units

Set scale minimum (default 0°C/32°F or 0 units)

inPt

Select input sensor

[nonE]

(See SENSOR SELECTION table, page 22)
NB. If Linear Input selected, start configuration from Level A.

unit [nonE]

°C °F bAr Psi Ph rh SEt

Select required operating unit from above options

LEVEL 3

OUTPUT CONFIGURATION

Note 1: Read only’ after initial configuration.

rSET ALL

full reset to factory settings

required to change

SP1.d

subsequently.

Note 2: Depending on the Model, SP1 and SP2 may be fitted with any of three output

types, RLY, SSd or Analogue (Specification on page 11/12) where appropriate,
these must be allocated during initial configuration. SP3 is always fitted with RLY.

Output Options Table

Model

SP1 Output

SP2 Output

SP3 Output

95111P

RLY

RLY

RLY

95001P

SSd

RLY

RLY

RLY

SSd

RLY

95221P

SSd

SSd

RL

Y

*95X11P

AnLG

RLY

RLY

RLY

AnLG

RLY

*95X21P

AnLG

SSd

RLY

SSd

AnLG

RLY

* Substitute for X in table above, Analogue options B = 4–20mA, C = 0–5V, D = 0–10V

Will be affected by

dECP

settings in Level A

Re-transmission

* These models above offer the option of using the analogue output for Re-transmission.

Select

bAnd

or

bnd.2

value in

LEVL 1

to equal the full range setting in

LEVL A

and if

using SP1 output, set

int.t

and

dErt.t

in

LEVL 1

to off.

Example: Set-Up using a Model 95B11P to Re-transmit the 4-20 mA input, scaled 0 to 100
units. SP1 relay is used as the control output and SP2 analogue output is used for re-
transmission.

Note: Read in conjunction with Linear Input Set-up Procedure on page 6.

Function

Options

[Factory settings] shown in brackets

From initial power-up;

Set

inPt nonE

to

inPt Lin

unit nonE

to

unit SEt

(for example)

SP1.d nonE

to

SP1.d rLY

To scale the input, select

LEVL A

, then:

Set

dECP

to

000.0

(e.g. required resolution)

An.hi

to

100.0

An.Lo

to

0.0

hi.in

to

50

(ie 20mA)

Lo.in

to

10

(ie 4mA)

To align SP2 analogue re-transmission with SP1 control output, select LEVL 2 then:

Set

SP2.A

to

FS.hi

And in LEVL.1

Set

SEt.2

to

50

(ie 50% of display range)

bnd.2

to

100

(ie 100% of display range)

Finally, set SP1 setpoint value as required for process to start.

Using SP1 output for re-transmission

Set

int.t

to off

dErt

to off

rev.d

to

1d.2d

to invert SP1 output

SP1 Setpoint

to

midscale

burn

Sensor burn-out/break protection

Caution: Settings affect fail safe state.

SP1

SP2

[uP.SC]

Upscale

Upscale

dn.SC

Downscale

Downscale

1u.2d

Upscale

Downscale

1d.2u

Downscale

Upscale

Retransmission range is limited to the sensor full scale value (Example RTD = 400C/752F).

LEVL 3

LEVEL 2 CONTINUED

English