Page 23: In.1 in.16

g
The same linearization table is used for input 1 and input 2.
6.2
Input scaling
Scaling of input values is possible. After any linearization, measurement value correction is according to the offset or
two-point method.
g
When using current or voltage signals as input variables for
InP.x, the input and display values should
be scaled at the parameter level. Specification of the input value of the lower and upper scaling point is in
units of the relevant physical quantity.
g
Parameters
InL, OuL, InH and OuH are visible only with ConF / InP / Corr = 3 selected.
Parameters
InL and InH determine the input range.
Example with mA:
InL= 4 and InH = 20 means that measuring from 4 to 20 mA is required (life zero setting).
Functions
KS 45
23
Input scaling
mA/V
phys.
quantity
mA / V
phys. quantity
OuH.x
OuL.x
InH.x
InL.x
Example for mA/V
Ou.16
Ou.1
.
.
.
.
.
.
In.1
In.16