2 configuration examples 37, 1 signaller (inverse)/ on-off controller 37, Signaller 37 – West Control Solutions KS 45 User Manual
Page 37: Inh.1 inl.1 sp.lo sp sp.hi, Sh out.1â inp.1к
Advertising

7.2
Configuration examples
7.2.1
Signaller (inverse)/ On-Off controller
ConF / Cntr: SP.Fn
=
0
setpoint controller
C.Fnc
=
0
signaller with one output
C.Act
=
0
inverse action (e.g. heating applications)
ConF / Out.1: O.Act
=
0
action
Out.1 direct
Y.1
=
1
control output Y1 active
PArA / Cntr: SH
=
0...9999
switching difference (symmetrical to the trigger
point)
PArA / SEtP: SP.LO
=
-1999...9999 setpoint limit low for SPeff
SP.Hi
=
-1999...9999 setpoint limit high for SPeff
g
For direct signaller action, the controller action must be changed (
ConF / Cntr / C.Act = 1 )
Controlling
KS 45
37
Configuration examples
setpoint
output
process value
SH
InH.1
InL.1
SP.LO
SP
SP.Hi
100%
0%
SH
Out.1Â