2 2-point controller (inverse) 38, Point controller 38, Inh.1 inl.1 sp.lo sp sp.hi out.1â inp.1ê – West Control Solutions KS 45 User Manual
Page 38
Advertising

7.2.2
2-point controller (inverse)
ConF / Cntr: SP.Fn
=
0
setpoint controller
C.Fnc
=
1
2-point controller (PID)
C.Act
=
0
inverse action (e.g. heating applications)
ConF / Out.1: O.Act
=
0
action
Out.1 direct
Y.1
=
1
control output Y1 active
PArA / Cntr: Pb1
=
0,1...9999
proportional band 1 (heating)
in units of phys. quantity (e.g. °C)
ti1
=
1...9999
integral time 1 (heating) in sec.
td1
=
1...9999
derivative time 1 (heating) in sec.
t1
=
0,4...9999
min. cycle time 1 (heating)
PArA / SEtP: SP.LO
=
-1999...9999
setpoint limit low for SPeff
SP.Hi
=
-1999...9999
setpoint limit high for SPeff
g
For direct action, the controller action must be changed (
ConF / Cntr / C.Act = 1 ).
Controlling
Configuration examples
38
KS 45
InH.1
InL.1
SP.LO
SP
SP.Hi
Out.1Â
InP.1Ê
100%
0%
PB1
setpoint
output
process value