Operation – West Control Solutions KS 92-1 Programmer manual User Manual

Page 14

Advertising
background image

Name

Description

Reason

Possible remedial action

SSr

Heating current

short circuit (SSR)

- Current flow in heating circuit

with controller off

- SSR defective

- Check heating current circuit
- If necessary, replace solid-state relay

LooP

Control loop alarm

(LOOP)

- Input signal defective or not

connected correctly

- Output not connected correctly

- Check heating or cooling circuit
- Check sensor and replace it, if necessary
- Check controller and switching device

AdA.H

Self-tuning heating

alarm

(ADAH)

- See Self-tuning heating error

status

- see Self-tuning heating error status

AdA.C

Self-tuning heating

alarm cooling

(ADAC)

- See Self-tuning cooling error

status

- see Self-tuning cooling error status

LiM.1

stored limit alarm 1 - adjusted limit value 1 exceeded - check process

Lim.2

stored limit alarm 2 - adjusted limit value 2 exceeded - check process

Lim.3

stored limit alarm 3 - adjusted limit value 3 exceeded - check process

Inf.1

time limit value mes-

sage

- adjusted number of operating

hours reached

- application-specific

Inf.2

duty cycle message

(digital ouputs)

- adjusted number of duty cycles

reached

- application-specific

E.5

Internal error in DP

module

- self-test error
- internal communication

interrupted

- Switch on the instrument again
- Contact West service

dp.1

No access by bus

master

- bus error
- connector problem
- no bus connection

- Check cable
- Check connector
- Check connections

dp.2

Faulty configuration - Faulty DP configuration

telegram

- Check DP configuration telegram in

master

dp.3

Inadmissible parame-

ter setting telegram

sent

- Faulty DP parameter setting

telegram

- Check DP parameter setting telegram in

master

dp.4

No data communica-

tion

- Bus error
- Address error
- Master stopped

- Check cable connection
- Check address
- Check master setting

g

Saved alarms (Err-LED is lit) can be acknowledged and deleted with the digital
input di1/2/3, the è-key or the Ò-key.
Configuration, see page 36:

ConF / LOGI / Err.r

g

If an alarm is still valid that means the cause of the alarm is not removed so far
(Err-LED blinks), then other saved alarms can not be acknowledged and deleted.

Operation

Error list / Maintenance manager

14

KS 90-1

p / KS 92-1

p