7.3.2 Programmer set-up:

The instrument is factory-configured as a program controller. The following set-
tings must be checked:

w Set-point function

For using the controller as a programmer, select parameter SP.Fn = 1 / 9 in
the ConF menu (

r

page 23).

w Time base

The time base can be set to hours:minutes or minutes:seconds in the ConF
menu; parameter t.bAS (

r

page 24).

w Digital signals

For assigning a control output, program end or the operator call as a digital
signal to one of the outputs, set parameter P.End, PrG1 … PrG4 or CALL
to 1 (

r

page 30-33) for the relevant output OUT.1 ...OUT.6 in menu ConF

(

r

page 30-33).

w Programmer operation

The programmer can be started, stopped and reset via one of the digital inputs
di1..3. Which input should be used for each function is determined by
selecting parameters P.run and P.oFF = 2 / 3 / 4 in the ConF menu
accordingly (

r

page 35, 36).

g

To permit programmer operation via the front panel, parameter di.Fn (ConF
menu; Logi

r

page 36) must be configured for key function.

Further settings, which affect the programmer display layout and operation are
only possible using the BlueControl software (see picture below and page 37/38).

Programmer level

KS 90-1

p / KS 92-1

p

63

Programmer description