Parameters 54, Inp.1, Inp.2 – West Control Solutions KS 92-1 Programmer manual User Manual
Page 54: Inp.3, Parameter setting level

g
Resetting the controller configuration to factory setting (Default )or
resetting to the customer-specific default data set
r chapter (page )
Parameter setting level
Parameters
54
KS 90-1
p / KS 92-1
p
q
InP.1
Name
Value range Description
Default
InL.1
-1999...9999
Input value for the lower scaling point
0
OuL.1
-1999...9999
Displayed value for the lower scaling point
0
InH.1
-1999...9999
Input value for the upper scaling point
20
OuH.1
-1999...9999
Displayed value for the lower scaling point
20
t.F1
0,0...9999
Filter time constant [s]
0,5
Etc.1
0...100 (°C)
32...212 (°F)
External cold-junction reference temperature (external TC)
OFF
q
InP.2
Name
Value range Description
Default
InL.2
-1999...9999
Input value for the lower scaling point
0
OuL.2
-1999...9999
Displayed value for the lower scaling point
0
InH.2
-1999...9999
Input value for the upper scaling point
50
OuH.2
-1999...9999
Displayed value for the upper scaling point
50
t.F2
0,0...9999
Filter time constant [s]
0,5
q
InP.3
Name
Value range Description
Default
InL.3
-1999...9999
Input value for the lower scaling point
0
OuL.3
-1999...9999
Displayed value for the lower scaling point
0
InH.3
-1999...9999
Input value for the upper scaling point
20
OuH.3
-1999...9999
Displayed value for the upper scaling point
20
t.F3
-1999...9999
Filter time constant [s]
0
Etc.3
0...100 (°C)
32...212 (°F
External cold-junction reference temperature (external TC)
OFF
q
Lim
Name
Value range Description
Default
L.1
-1999...9999
Lower limit 1
10
H.1
-1999...9999
Upper limit 1
10
HYS.1
0...9999
Hysteresis limit 1
1
dEl.1
0...9999
Alarm delay from limit value 1
0
L.2
-1999...9999
Lower limit 2
OFF
H.2
-1999...9999
Upper limit 2
OFF
HYS.2
0...9999
Hysteresis limit 2
1
dEl.2
0...9999
Alarm delay from limit value 2
0
L.3
-1999...9999
Lower limit 3
OFF
H.3
-1999...9999
Upper limit 3
-32000
HYS.3
0...9999
Hysteresis limit 3
1
dEl.3
0...9999
Alarm delay from limit value 3
0
HC.A
-1999...9999
Heat current limit [A]
50