Calibrating level 49, Calibrating level 49 - 51, Calibration 49 – West Control Solutions CI 45 User Manual
Page 49
Advertising

.
9
Calibrating level
Adaptation of the measurement value is possible in the calibrating menu (
CAL).
g
Measured value correction (
CAL) is accessible only, if ConF / InP/ Corr = 1 or 2 was selected.
Two methods are possible :
•
offset correction
•
2-point correction
g
Values
InL.x and InH.x are displayed with one digit behind the decimal point. However, the full
resolution is used as a reference for calculating the correction.
g
The easiest way to delete the corrective values is by switching off the measured value correction
Corr = 0 or by setting the scaling parameters to a linear curve.
+
Values
InL.x and InH.x indicate the actual measurement value. Output values OuL.x and
OuH.x start with the previously adjusted value.
Calibrating level
UNIFLEX CI 45
49
Advertising