1 offset correction 50, Offset correction 50, Offset-correction 50 – West Control Solutions CI 45 User Manual
Page 50

9.1
Offset correction
Offset correction shifts the input value by a pre-defined value.
Parameter setting:
(
ConF/ InP/ Corr =1 ):
w
On-line offset correction at the process is possible.
InL:
The actual input value of the scaling point is displayed.
The correction function is activated by means of keys ÈÌ ; the display changes from Off to
the measured value.
The operator must wait, until the process is at rest.
Subsequently, the input value has to be confirmed by pressing key ô .
OuL:
The scaling point display value is indicated.
The operator can correct the display value by pressing keys ÈÌ. Subsequently, he presses key
ô to confirm the display value.
Calibrating level
50
Offset correction
UNIFLEX CI 45
r
3 sec.
r
PArA
CAL
r
r
InP
r
InL
r
r
OuL
r
End
r
ConF
rr
InL
r
450.3
450.0
дььь
ф
ф
ф
ф
ф
ф
ф
X
standard setting
offset correction
InL
OuL
new
display
OuL
old