West Control Solutions MRC 7000 Recorder Manual User Manual
Page 29

29
6
Decimal Position
dPoS
0=None
0
1=One decimal position
2=Two decimal positions
3=Three decimal positions
RTD and thermocouple inputs
are limited to either 0 or
1 decimal positions
7
Engineering Units
Euu
-9999 to 9999
1000
Upper Value (If Input
Select = 30, 31, 32, 33, 34)
8
Engineering Units
EuL
-9999 to 9999
0
Lower Value (If Input
Select = 30, 31, 32, 33, 34)
9
Hysteresis for
HyAo
0 to 300 degrees/units
3
Alarm Outputs
Width of Hysteresis Band
(See page 54 for definition)
10
Setpoint Upper Limit
SPuL
-9999 to 9999
1400
(Limit Only)
11
Setpoint Lower Limit
SPLL
-9999 to 9999
0
(Limit Only)
12
Process Rounding of Prnd 0=No Rounding
0
Displayed value
1 to 100 degrees/units
13
Display Filter Factor
dFF
1=No filtering
1
1 to 20 units
(number of values
averaged)
14
Process Filter Factor
PFF
1 = No filtering
1
1 to 20 units
(number of values averaged)
15
Process Value Output
Pout
0=Not selected
0
(If Pout =0 then Pou and
1=Selected
PoL will not be displayed)
16
Process Output
Pou
-9999 to 9999 degrees/units
2000
Upper Value
17
Process Output
PoL
-9999 to 9999 degrees/units
0
Lower Value
18
Chart Range Upper Value
Cru
-9999 to 9999 degrees/units
200
19
Chart Range Lower Value
CrL
-9999 to 9999 degrees/units
0
20
Pen Action on
PAEC
0=Pen goes to 0%
1
Error Condition
of chart span
1=Pen goes to 100%
of chart span
Pressing the SCROLL key with the PAEC parameter value displayed in the Pen 1 window will
advance the display of a single pen instrument to the unit parameters. Pressing the SCROLL
key with the PAEC parameter displayed in the Pen 1 window of a two pen instrument will
advance the display to be inPS in the Pen 2 window. The Pen 2 Program mode parameter
selections can be made now. Pressing the SCROLL key with the PAEC parameter value
displayed in the Pen 2 window will cause the display to advance to the unit parameters.
DISPLAY AVAILABLE
FACTORY YOUR
STEP
DESCRIPTION
CODES SETTINGS
SETTING SETTING